The EL3446-0011 EtherCAT Terminal enables measurement of
all relevant electrical data in the supply grid and performs simple
pre-evaluations. Since the EL3446-0011 itself has no voltage
inputs, the measured voltage values are transmitted via EtherCAT
from an EL3443 to be installed once per network.
The current in the connectable phases – of which there are up
to six – is fed in via simple current transformers. All measured
currents and voltages are available as RMS values.

In the EL3446-0011. the active power and the energy consumption
for each phase are calculated. RMS values are available for voltage
U and current I as well as active power P, apparent power S,
reactive power Q, frequency f, phase shift angle cos φ, and
harmonics. The EL3446-0011 offers options for comprehensive
network analysis and energy management.
With 100 mA inputs, the EL3446-0011 is particularly suitable for
evaluating differential current transformers (such as the SCT4xxx)
and DC-capable current transformers.