The analog EL3356-0090 input terminal enables direct connection
of a resistor bridge or load cell in a 4- or 6-wire connection technology.
The ratio between the bridge voltage UD and the supply voltage UREF
is determined simultaneously in the input circuit and the final load value
is calculated as a process value on the basis of the settings in the terminal.
With automatic self-calibration (can be deactivated) and dynamic filters
the terminal with measuring cycles of 10 ms can be used for slow weighings
with high precision.

With the aid of the TwinSAFE SC technology (TwinSAFE Single Channel) it
is possible to make use of standard signals for safety tasks in any network
or fieldbus. To do this, EtherCAT I/Os from the areas of analog input, position
measurement or communication (4…20 mA, incremental encoder, IO-Link,
etc.) are extended by the TwinSAFE SC function. The properties typical for
the signals and the standard functions of the I/O components are retained.
TwinSAFE SC I/Os differ optically from standard I/Os by a yellow stripe on
the front of the housing.
The TwinSAFE SC technology enables communication via a TwinSAFE protocol.
These connections can be distinguished from the usual secure communication
via Safety over EtherCAT.
The data from the TwinSAFE SC components is fed via a TwinSAFE protocol to
the TwinSAFE Logic, where it can be used in the context of safety-relevant
applications. Detailed examples confirmed/calculated by the TÜV SÜD for the
correct application of the TwinSAFE SC components and the respective normative
classifications can be found in the TwinSAFE application manual.