The ED2889 digital output terminal connects the binary 24 V DC control
signals from the automation device on to the actuators at the process
level with electrical isolation.
The EtherCAT Terminal has 16 channels that indicate their signal state
via light emitting diodes (status LEDs). The power contacts are looped
through internally. In the ED2889 the outputs are supplied via the 0 V
DC power contact.

The connection technology is optimized for single-ended signals (common
reference point). To ensure error-free operation, all connected components
must use the same reference as the ED2889 terminal.
Special features:
• suitable for controlling different types of loads:
• resistive loads (e.g., resistors)
• inductive loads (e.g., relays, contactors, valves)
• capacitive loads
• max. output current of 0.5 A per channel
• ground switching
• short-circuit proof outputs: protection against overload or short circuit
• reverse polarity protection in the event of incorrect polarity of the supply voltage
The ED series EtherCAT Terminals have push-in connection technology which
makes wiring easy and tool-free.