The ED2807 digital output terminal connects the binary 24 V DC
control signals from the automation device on to the actuators at
the process level with electrical isolation. The EtherCAT Terminal
has 32 channels that indicate their signal state via light emitting
diodes (status LEDs). The power contacts are looped through
internally. In the ED2807 the outputs are supplied via the 24 V
DC power contact.

The connection technology is optimized for single-ended signals
(common reference point). To ensure error-free operation, all
connected components must use the same ground reference
as the ED2807.
Special features:
• suitable for controlling different types of loads:
• resistive loads (e.g., resistors)
• inductive loads (e.g., relays, contactors, valves)
• capacitive loads
• max. output current of 0.5 A per channel (∑ 10 A)
• positive switching
• short-circuit proof outputs: protection against overload or short
circuit
• reverse polarity protection in the event of incorrect polarity of the
supply voltage
The ED series EtherCAT Terminals have push-in connection technology
which makes wiring easy and tool-free.