Product Description
For critical process control applications where you can’t afford
interruptions, the DeltaV system offers controller redundancy.
The standby controller contains the same control strategies as
the active controller and the redundancy link transfers control
parameters to the standby controller to ensure it is ready to take
control if needed.
With redundancy enabled, each module will calculate the
required updates for the Standby controller when it executes.
These updates are transferred to the standby controller over
the redundancy link. These additional operations for controller
redundancy will typically reduce your CPU free time by
approximately 10%.
When a fault is detected, the standby controller can take over
without bumping the process control signals. The DeltaV Event
Chronicle stores a record of each switchover and the reason it
occurred (if the reason has been identified).
Replacing an existing standby controller is as simple as removing
the existing unit and installing a new controller. The active
controller will detect the standby and the system will automatically
commission and download the new hardware. A redundancy
license is required in addition to the redundant hardware. The
redundant controller appears in the Explorer window as a single
node, indicated by a redundant controller icon.
Switchover Detection
The redundant controllers continuously monitor themselves
and each other for conditions that require a switchover. Each
controller runs continuous self-test routines to determine their
ability to function. A hard failure of the active controller will trigger
an immediate switchover to the standby controller. The standby
controller also monitors the I/O bus traffic to detect if the active
controller stops functioning and failed to issue a switchover
command. This switchover requires a verification cycle, during
which time all output signals hold their values until the new active
controller begins executing control strategies.
Some of the events that can cause a switchover are:
•Hardware failure within the active controller
•Communications failure between the active controller
and I/O
•Communications failure on both control network ports of the
active controller
•Removal of the active controller from the carrier
•User request initiated from Diagnostic Explorer
System Compatibility
M-series, S-series and SZ controllers are all supported on
DeltaV v12.3 and beyond. PK Controllers are supported on
DeltaV v14.3 and beyond. For detailed version compatibility
see the Prerequisites section below.
Redundant controller pairs must be of the same series. For
example, M-series and S-series controllers cannot be connected
together as a redundant pair.
Although an SX controller can operate as a standby controller to an
SQ active controller, it is recommended that both the active and
standby controllers be of the same hardware. The SQ may not have
sufficient memory or CPU capacity to accept the configuration that
runs in an SX controller. This applies for MX and MQ controllers as
well, only mix controller types as a temporary condition during a
hardware upgrade.
The MQ, MX, SQ, SX and PK Controllers are all capable of
redundancy. For more information on these controllers, refer to
the respective controller product data sheet.
SZ Controllers are also capable of redundancy. For more
information on this controller, refer to the DeltaV SIS Electronic
Marshalling or DeltaV SIS IS Electronic Marshalling product
data sheets.
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved