The KONGSBERG DZ-110/U Transmitter Barrier Unit is designed to
safely provide signal interface and pow er supply to Kongsberg
instrumentation located in hazardous area. The unit connects
intrinsically safe 4-20 mA transmitters.

Principle of operation
The Transmitter Barrier is installed in safe area, designed to
limit the amount of energy that could appear in an electric circuit
that connects to instrumentation located in hazardous area.
The DZ-110/U is a single channel shunt diode safety barrier,
intended for energising a 2-wire, 4-20 mA signal transmitter
installed in hazardous area. A “current mirror” amplifier re
peats the transmitter current into an equal magnitude safe
side current. To prevent leakage through the zener diodes, the
voltage applied to the barrier section is regulated and limited
to a suitable level. Active current limiting is also incorporated to
prevent fuse blow-out during accidental shorting of the transmit
ter circuit.
Installation
The Transmitter Barrier is typically installed in the processing
cabinet in control room. The DZ-110/U is equipped with blue
coloured terminals 4 and 5/6 for connection of the intrinsically
safe circuit in hazardous area. Terminals 2 and 3 connects the
Transmitter Barrier to an analogue input channel in the moni
toring system. The Transmitter Barrier shall be grounded to the
Intrinsically Safe busbar in the system (6), by minimum a 1.5
mm2 cable.
The DZ-110/U snaps to a TS-32 or a TS-35 mounting rail (ac
cording to DIN46277). End stoppers shall be used to support
the units.
Special conditions for safe use :
1. The separation distance of minimum 50 mm between
intrinsically and non-intrinsically safe circuits has to be
observed for the final installation in a cabinet.
2. The DZ-110/U has to be installed in a cabinet with a degree
of protection depending on installation, but at least IP22.
3. The ambient temperature range for the DZ-110/U is -20 °C ≤
Ta ≤ +70 °C
4. A grounding/earthing bar must be mounted at the
intrinsically safe side of the barrier. Terminal 3 on each
barrier must be connected to this bar by a 1.5 mm2
(minimum) cable.
Safety instruction:
For safety instruction see the document 373874 K-Gauge Ex I
Safety instructions.
FEATURES
• Intrinsically safe connection of 4 - 20 mA transmitters to safe
area
• Snap-on installation to DIN rail (TS-32 or TS-35)
• Small size
• ATEX, IECEx and type approved