INTRODUCTION
The DXCB-2 De-Excitation/Crowbar Module protects the generator field
and exciter circuits by providing a low impedance path for currents that
would otherwise cause excessively high transient voltage or damaging
arcs. A DXCB-2 module can be operated in one of two modes: de-
excitation (DX) or crowbar (CB).
In DX mode, the DXCB-2 module provides a path for the generator field
current when its field breaker is opening or when the normal path is not
available.
In CB mode, the DXCB-2 module provides a low-resistance path for large
positive voltages across the generator field and exciter bridge. Generator
pole-slip is one source of high voltage.
The enclosure of the DXCB-2 offers electric shock protection from incidental
contact. An identical footprint and functional compatibility make for simple
replacement of a DXCB with a DXCB-2.

DXCB-2 Models
Three versions of the DXCB-2 module are available. Part number 9500900100
is rated for up to 600 Vdc nominal field voltage and can conduct up to
2.000 Adc for one second. Part number 9500900101 is rated for up to 1.000
Vdc nominal field voltage and can conduct up to 5.000 Adc for one second.
Part number 9500900102 has identical ratings to part number 9500900101
but has a higher range of jumper-selectable trip voltage values.
Reference Table 3 for jumper-selectable trip voltages for each model.
SAFETY
As with all electrical equipment, appropriate safety measures must be taken
when dealing with excitation equipment. High voltage is present within the
excitation cubicles; their magnitudes depend upon the particular system.
Opening the sources (e.g., disconnecting device 41) does not completely
disconnect the high voltages.
As long as the machine is still physically connected to the system, there is
a possibility that a safety hazard exists.
Every precaution must be taken when working at the excitation control
switchgear to ensure that all high voltages are isolated and avoided by
test personnel. In addition to the machine terminal voltage (460 Vac or
greater) at the excitation transformer, there may be other sources of power
entering the cubicles, such as 125/250 Vdc and/or 120/240 Vac used to
feed certain devices. A good rule to follow is to assume that all connections
are live and dangerous until proven otherwise and to avoid all body contact
with any of these voltages.
INSTALLATION
The DXCB-2 is typically preinstalled in the excitation control system. If
replacement is necessary, carefully label and document each of the
connections to the DXCB-2 in order to properly reconnect the new module.
The DXCB 2 must be monitored and adjusted to fit the specific application
at initial startup, whether it is a new unit or a replacement.