INTRODUCTION
The DXCB-2 De-Excitation/Crowbar Module protects the generator
field and exciter circuits by providing a low impedance path for
currents that would otherwise cause excessively high transient
voltage or damaging arcs. A DXCB-2 module can be operated in
one of two modes: de-excitation (DX) or crowbar (CB).
In DX mode, the DXCB-2 module provides a path for the generator
field current when its field breaker is opening or when the normal
path is not available.
In CB mode, the DXCB-2 module provides a low-resistance path
for large positive voltages across the generator field and exciter
bridge. Generator pole-slip is one source of high voltage.

The enclosure of the DXCB-2 offers electric shock protection from
incidental contact. An identical footprint and functional compatibility
make for simple replacement of a DXCB with a DXCB-2.
DXCB-2 Models
Three versions of the DXCB-2 module are available. Part number
9500900100 is rated for up to 600 Vdc nominal field voltage and
can conduct up to 2.000 Adc for one second.
Part number 9500900101 is rated for up to 1.000 Vdc nominal field
voltage and can conduct up to 5.000 Adc for one second.
Part number 9500900102 has identical ratings to part number
9500900101 but has a higher range of jumper-selectable trip voltage
values.
Reference Table 3 for jumper-selectable trip voltages for each model.
SAFETY
As with all electrical equipment, appropriate safety measures must be
taken when dealing with excitation equipment. High voltage is present
within the excitation cubicles; their magnitudes depend upon the
particular system. Opening the sources (e.g., disconnecting device 41)
does not completely disconnect the high voltages.
As long as the machine is still physically connected to the system, there
is a possibility that a safety hazard exists.
Every precaution must be taken when working at the excitation control
switchgear to ensure that all high voltages are isolated and avoided by
test personnel. In addition to the machine terminal voltage (460 Vac or
greater) at the excitation transformer, there may be other sources of
power entering the cubicles, such as 125/250 Vdc and/or 120/240 Vac
used to feed certain devices. A good rule to follow is to assume that all
connections are live and dangerous until proven otherwise and to avoid
all body contact with any of these voltages.
INSTALLATION
48.6 lb (22.1 kg)
16.25 x 11.22 x 10.52 inches
(412.6 x 285.0 x 267.2 millimeters)
The DXCB-2 is typically preinstalled in the excitation control system. If
replacement is necessary, carefully label and document each of the
connections to the DXCB-2 in order to properly reconnect the new module.
The DXCB 2 must be monitored and adjusted to fit the specific application
at initial startup, whether it is a new unit or a replacement.