transmitted when changes are detected.
Sequence of Events
Each DPU includes a built-in Sequence-of-Events (SOE) recorder that can
monitor up to 512 discrete inputs. These inputs are scanned 1.000 times a
second and state changes are time stamped with 1 ms resolution and stored in
the DPU's 10.000-event buffer. Each input has a separately configurable
digital filter for contact debounce.
Distributed Processing Unit Specifications
Operating temperature range
Storage temperature range
Relative humidity range
Power requirements
Current:
Powering the DPU
0 to 60 degrees C
(-)25 to 70 degrees C
5 to 90% noncondensing
24 Vdc ±4 Vdc
0.9 A @ 24 Vdc
The DPU operates from the main redundant 24 Vdc power supply system in
the maxDNA system cabinets.
Mounting the DPU
The DPU is mounted on the Input/Output (I/O) backplane with maxPAC and
earlier Model 564 Input/Output modules.
Positioning the DPU in a Standard maxPAC Chassis
The DPU must be mounted in the left most position of the Model IOP rack to
allow for the best airflow. The Backup cable and Ethernet communications
cables should be laced to the left side of the chassis with at least a 1 inch
bend radius to allow for easy removal of the DPU, while limiting the strain
on the RJ45 connectors.
When using a second DPU for backup, it should be mounted vertically
beneath the primary DPU for ease of connection of the two-foot backup
cable. The cable is to be held in place by tying to the cable hold downs on
the side of the IOP rack.
The DPU is designed to allow installation and removal with the +24 V dc
power supply turned on.
Positioning the DPU When Upgrading
The DPU can be mounted on the right side of a Six Wide maxPAC chassis or
any slot of the Four Wide Model 564 chassis. In either case, remove all
mounting hardware and termination panels that supported the earlier model
DPU. Install a Chassis 4 Wide maxPAC adapter (Metso Automation
#047350) in the cleared space using the two mounting holes located in the
back panel metal frame.
If the previous DPU was a DPU4E, the Ethernet cables that were plugged
into the termination panel can be plugged directly into the front panel of the
DPU card. Make sure that the settings of the Ethernet switch match the setup
file. See Chapter 5 for the configuration setup.
If the previous DPU was a DPU3. DPU4A, or DPU4B; new Ethernet
switches and cables will need to be installed. Consult the factory for details
about this type of upgrade.
In all upgrade situations, the backup cable must be replaced with a DPU4F
backup cable (Metso Automation # 050292).
Mounting Procedures
Before mounting any hardware, refer to the cabling and field wiring sections
of Publication 278596. maxPAC Hardware Reference Guide, and Publication
278563. Model IOP Input/Output System Installation and Preparation.
To install the DPU in the rack, refer to Chapter 7 Starting the DPU.