- CT current sensing: 1 A / 5 A secondary for metering and paralleling compensation.
Outputs
- PWM‑driven DC field output: 32/63/125 Vdc, 15 Adc continuous, 30 Adc 10‑sec forcing.
- 3 programmable relay outputs + watchdog relay for alarm & fault signalling.
Generator Paralleling Functions
- Reactive droop or cross‑current differential compensation for multi‑generator parallel operation (uses 1 A /5 A current transformers).
- Line‑drop compensation.
- Voltage‑Matching: Match generator RMS voltage to bus voltage within ±0.15% before synchronizing closing breaker.
Software & Accessories
Software Tools
- BESTCOMS for Windows: Full configuration, PID tuning, live metering, download SER events and oscillography data. Two‑level password security for parameter modification.
- BESTWAVE‑32: COMTRADE waveform file viewer.
Key Accessories
- Front‑panel mounting bracket (P/N 9360107100)
- Dual‑unit tracking interconnection cable
- ICRM‑15 Inrush‑Current Reduction Module
- Freewheeling diode module for redundant dual‑DECS‑200 setup
- IDP‑800 remote color touch‑screen HMI: Remote monitoring & adjustment over RS‑485 link.
Frequently Asked Questions (FAQ)
Q: What is DECS‑200‑1C used for?
A: It is a full‑featured digital excitation regulator (digital AVR) for synchronous generators, covers standalone and grid‑parallel operating scenarios.
Q: Does DECS‑200‑1C support bumpless transfer?
A: Yes. Internal auto‑tracking between operation modes; optional external auto‑tracking for primary‑backup dual DECS‑200 units.
Q: Can DECS‑200‑1C monitor brushless exciter diodes?
A: Yes, EDM Exciter Diode Monitor detects open and shorted rotating diodes on brushless generators.
Q: What communication protocols are supported?
A: RS‑232 ASCII (local PC), RS‑485 Modbus‑RTU for SCADA/PLC integration.