4 Isolated Analog Outputs Module
The 4 Isolated Analog Outputs module provides four analog
outputs that can be individually jumper configured for 4 to
20 mA or 1 to 5 Vdc isolated operation. Analog outputs are
electrically isolated from the CPU power system. Calibration
data for each channel is stored in an onboard EEPROM for
both current and voltage mode configurations. The 4
Isolated Analog Outputs module is available with local or
remote terminations.
Local or Remote Terminations
All analog I/O modules are available factory configured for
either local terminations that consist of two 10-point
terminal block assemblies or remote terminations that
consist of two 14-pin mass termination headers.
Terminations are pluggable and accept a maximum wire
size of 14 AWG (American Wire Gauge).
Remote terminations provide a convenient alternative to
the standard direct connect termination. Remote
terminations allow a concentration of electrical connections
from one or more controllers to be located in a single area,
such as the rear of a 19-inch cabinet. For more information
on remote terminations, refer to Product Date Sheet