High density solutions
Cyberex offers the complete current limiting, selectively coordinating solution for
your high power, high efficiency data center
The industry demand to increase data center
efficiency and push the limits of power density at
the rack has introduced new design trends. While
one proposed solution, raising the distribution
voltage in the whitespace, helps meet these
demands, data center systems designed at higher
voltages (415V, 480V) provide system owners and
designers with a new set of challenges and
concerns to overcome.
Selective coordination,increased arc flash potential, protecting sensitive
IT equipment and complying with SCCR and IR
code requirements take center stage. These
heightened concerns are mainly driven by the
removal of a transformer and the potential
increase in available fault current when compared
to traditional 208V designs. With the high available
fault currents, average main and branch breaker
combinations will not allow branch breakers to trip
independently of the main, forcing the shutdown
of an entire panelboard to clear an overcurrent on a
branch circuit. This lack of coordination will in turn
cause unnecessary downtime to critical server loads.