Eaton’s Current Limiting Reactor (CLR) is a power conditioning system that limits
fault current under short-circuit conditions, helping to support overall NFPA-70E
and NFPA-75 safety. The CLR is to be installed between a switchboard and
switchgear and will be electrically connected to them with flexible busbar
connectors.

Ratings
• Amperage: 600 – 6300A
• Input specs: 3-phase, 3 or 4 wires + ground
• Input and output voltage:
• @ 50 Hz: 415. 400. 380VAC
• @ 60 Hz: 480. 415. 400VAC
Enclosure
• NEMA 1
• Frame ground
• Enclosure front infrared door (input and output terminal) smallest footprint in the industry
Optional side cabinet
Provides space for a cable distribution with bracket.
• 24”W x 36”D
• 30”W x 36”D
• 24”W x 48”D
• 30”W x 48”D
Temperature monitor
• Temperature: thermocouples, normally open and normally close on each single-phase
reactor with terminal block at the top of the units for fast installation.
• Optional PT100 sensor
• Input specs: 3-phase, 3 or 4 wires + ground
Operating conditions
• Operating temperature: ambient 0°C to 40°C
• Storage temperature: ambient -10°C to +40°C
• 50 Hz operating range: 47-53 Hz
• 60 Hz operating range: 57-63 Hz
Features
• Copper wound construction
• Single-phase reactor
• Prospective short circuit current standard 65kAIC up to 100kAIC
• Let-through current standard 14kAIC, down to 10kAIC
• Routine test: - Hi-pot test at 10kV, 3-phase
• Phase-to-phase and phase-to-GND
• Measure inductance test
• Load test (3-phase)
• Insulation resistance test
• Special test:
• Short circuit test
• Hi-pot test
• 10kV phases and ground
• Heat run test
• UL witness test
• Audible noise test
• Solid neutral busbar
• Frame ground
• Listed UL/CSA, CE mark, UL1561. UL891. IEEE C57.16. IEC60076-6
• Compliance: NFPA-70E, NFPA-75 safety and ISO standard.