The CIOC carrier is mounted to the top of a vertical DIN
rail and up to eight CHARM Baseplates are mounted below
it, snapping easily to the DIN rail as they are connected to
each other. The bus termination assembly is attached at the
bottom. A standard DIN-rail lock is used to keep the entire
assembly in place.
A pair of CIOCs installs on the carrier and communicates
over a redundant Ethernet network with up to four
controllers, allowing great flexibility and ease of system
expansion. Communication modules are available for
copper and fiberoptic media.
Each baseplate is ordered with 12 terminal blocks: standard
terminal blocks, fused injected power terminal blocks, or
relay output terminal blocks.
Electronic Marshalling eliminates the need to partition the
I/O wiring to specific channels based on signal type. Simply
connect field signal multi-cores in an orderly fashion as
desired. Install the appropriate CHARM to complete the
field circuit and the signal is ready to be used by any one of
four controllers. No cross-wiring required.
Each CHARM acts as a circuit protection device and field
wiring disconnect. Signals are inherently current-limited
to protect against wiring faults to ground. Each CHARM
provides surge protection to meet industry standards in
the area of EMC. Under extreme overvoltage conditions
due to incorrect field wiring, the CHARM will act as a fuse to
protect adjacent channels. Signal faults are thus isolated to
the single CHARM.