Function
CC-USCA01 is a back plane assembly which can accommodate 16 signal conditioning modules. Field side terminals of
each channel is provided with integrated fuse and knife disconnect function. The safety system side interface is provided
through a single System Integration Cable (SIC) which connects all 16 channels. CC-USCA01 is DIN rail mountable.
Features
• Integrated fuse and disconnect function for field side interfaces
• Fuse blown indication for field side fuses
• Disconnect function with current measurement terminals
• 2 wire or 3 wire interface towards field for each channel
• 24V DC power with LED indication
• System Integration Cable (SIC) for 16 channel system side interface
• Screw less assembly to the base plate
• Compatibility with Honeywell IO families: Series C module, Universal IO, Universal Safety IO
Detail Specifications – Universal Signal Conditioning Assembly