The BE1-GPS100 is a multifunction, programmable numerical protection, meter, and control
relay. Functions provided include three phase voltage controlled, voltage restrained, or
standard overcurrent, phase residual and independent ground overcurrent, negative sequence
overcurrent, breaker failure, over/underfrequency, phase over/undervoltage, zero sequence
over/undervoltage, and negative sequence overvoltage, forward or reverse power, loss of
excitation, volts per hertz, sync check, sensitive third harmonic ground fault monitoring, breaker
monitoring and control and metering functions, all in an integrated system.

ADVANTAGES
BESTlogic provides the user with very high flexibility in configuring a protection and control
system.
Substantial functionality in a small package, useful where space is very limited but high
functionality is needed.
Programmable LCD display allows the relay to replace local indication and control func
tions, such as panel metering, alarm annunciation, and control switches.
Three independent communication ports with protocol support allows integration with
distributed control systems.
Provides optional separate ground current input for those applications where this is
required.
Includes frequency tracking and voltage restrained overcurrent for backup and cogenera
tion applications.
Includes Real Time Clock with 8 hour capacitor ride through and optional battery backup.
Available in fully drawout half rack case. Two Basler Electric half rack IEDs (Intelligent
Electronic Devices) can be dovetailed together to mount in a standard 19-inch equipment
rack with no special mounting hardware.
Available in fully drawout S1 case with test paddle. The S1 case, with available adapter
plates, fits cutout, drilling and behind panel projection dimensions for common Basler
Electric, GE and Westinghouse unit case relays.
PROTECTION
Phase and Neutral Instantaneous Overcurrent
elements with settable time delay: 50TP, 50TN
Phase, Neutral, and Negative Sequence Time
Overcurrent elements: 46. 51P, 51N, 151N
Phase overcurrent element (51P) includes capabil
ity of voltage restraint or voltage control.
Internally calculated phase residual, 3I0. available
on all relays. Optional independent ground input
available. Neutral overcurrent elements (50TN, 51N,
151N) monitor either ground or calculated residual.
Negative sequence overcurrent element (46)
includes algorithm for timing based on generator
K factors or may use standard TOC curves.
All U.S. and IEC timing curves plus user program
mable curve.
Phase Undervoltage and Overvoltage elements:
27P, 127P, 59P, 159P. Elements use a 1 of 3. 2 of
3. or 3 of 3 logic, and monitor either line-line or line
ground voltages.
Auxiliary Undervoltage and Overvoltage elements:
27X, 127X, 59X, 159X. Elements monitor either
fundamental or third harmonic on the optional
auxiliary 4thVT input, or fundamental phase
residual, 3V0. of the phase inputs.
Negative Sequence Overvoltage element: 47
Overexcitation, Volts per Hertz element: 24
Four Under/Overfrequency elements: 81. 181. 281. 381
Forward/Reverse Power: 32. 132
Loss of Excitation (offset sloped VAR flow algo rithm): 40Q, 140Q
Breaker Failure protection function: BF
4 general purpose logic timers: 62. 162. 262. 362
Inadvertent energization protection using 50
elements supervised by 81 and/or 27 elements
100% stator ground fault protection using auxiliary
voltage elements for ground overvoltage and 3rd
harmonic ground undervoltage
Sync check and/or dead bus close supervision
25. 27X (Requires optional 4th VT sensing circuit)
Programmable Logic using BESTlogic
Two protection settings group controllable via relay
logic, 43 Aux switches, and hardwired inputs.
Setting group selection may control tripping logic.
Fuse loss detection (60FL) protects against false
trip due to loss of voltage sensing.
CONTROL
Virtual breaker control switch controllable from
both HMI and com. ports: 101
Four virtual selector switches controllable from
both HMI and com. ports: 43. 143. 243. 343
Communication port control of 101 and #43
switches allows for SCADA control of relay and
breaker.
INSTRUMENTATION
Real time A, B, C phase current, voltage; fre