Overview
The BE1-59N provides accurate 100% stator-ground protection for ungrounded
and high-resistance grounded generators.

Features
• Provides 100% stator ground fault protection.
• 100/120 Vac or 200/240 Vac nominal sensing input.
• Four sensitivity ranges for overvoltage: 1 to 20 and 10 to 50 Vac for a
100/120 Vac input and 2 to 40 and 20 to 100 Vac for a 200/240 Vac
input.
• Four sensitivity ranges for undervoltage: 0.1 to 2.5 Vac and 0.5 to 12
Vac for a 100/120 Vac input and 0.2 to 5 Vac and 1 to 24 Vac for a
200/240 Vac input.
• Instantaneous, definite, and inverse time characteristics.
• 40 dB harmonic filtering.
• Low sensing input burden.
• Power supply status contact.
Benefits
• Limit generator damage with 100% stator ground-fault protection.
• Wide range of applications covered with four overvoltage and four
undervoltage setting ranges.
• Meet protection timing requirements with instantaneous-, definite-, and
inverse-time characteristics options.
• Accurate detection of fundamental and third harmonic content using 40
dB harmonic filtering.
• Minimized potential transformer (PT) costs as a result of low sensing
burden.
• Reduced battery load with low burden power supply.
• Accurate, repeatable, and reliable operation.
• Simple human-machine interface (HMI) provides clear and intuitive
settings for easy configuration.
• LED targets provide clear annunciation of status.
• Easily perform in-case system and device tests using test plugs.
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved