The BE1-47N Voltage Phase Sequence Relay provides protection for rotating equipment
from the damaging effects of excessive negative sequence voltage resulting from phase
failure, phase unbalance and reversed phase sequence.

ADVANTAGES
• Responds to true negative sequence voltage component.
• Unaffected by frequency variations of ±5 Hz.
• Negative Sequence Voltage adjustment range of 2 - 32 percent.
• Optional Over and Undervoltage measuring elements.
• Low sensing and supply burdens.
• Instantaneous, Definite and Inverse time delay characteristics available for
each measuring element.
• Qualified to the requirements of
— IEEE C37.90.1-1989 and IEC 255 for surge withstand capability;
— IEC 255-5 for impulse.
• UL recognized per Standard 508. UL File #E97033.
• Gost R certified per the relevant standards of Gosstandart of Russia
• Five year warranty.
APPLICATION
PURPOSE
The BE1-47N is designed to protect three-phase ma
chines against damage caused by phase failure, reverse
phase sequence phase unbalance, undervoltage and
overvoltage.
The BE1-47N responds to the negative sequence voltage
which results from a fault or misconnection on a balanced
three-phase system.
The BE1-47N detects reverse phase connection of lines,
transformers, motors, generators, and synchronous con
densers and is often applied in automatic transfer schemes
to assure connection of proper phase rotation as well as
voltage conditions. The Negative Sequence Voltage Re
lay is recommended for all important buses supplying
motor loads. When used in motor protection, the relay will
provide protection by preventing start-up of the motor for
open phase or reverse phase conditions and by tripping
the motor off-line for phase unbalance, undervoltage or
overvoltage conditions.
Negative sequence voltage is the result of any unequal
phase condition. This can be due to unequal single-phase
loads on the system or unequal transformer impedances
between the phases. A 1% - 2% negative sequence level
can normally be expected in an industrial supply. Any
significant increase above this level is an indication of a
power service problem that could lead to serious plant
problems. The BE1-47N has the ability to detect negative
sequence voltage levels of this magnitude.
Undervoltage and voltage balance relays have tradition
ally been applied for the protection of induction motors
from operating with one phase open. These relays may
not reliably detect this condition due to the back emf of
the motor on the open phase. However, an induction
motor, with a starting current of 6 per unit, will generate
a negative sequence voltage of 16% if fully loaded when
a fuse blows. The negative sequence voltage will be
somewhat reduced if the motor is not fully loaded. The
sensitivity of the BE1-47N and its insensitivity to fre
quency will provide reliable protection for motors.
Motor losses and current unbalance increase with the
negative sequence voltage level. The increased loss,
due to negative sequence voltage, is not a function of
motor load but is independent. A machine operating
with 3.5% negative sequence voltage will have its stated
losses increased by 25%. A blown fuse on a power factor
correction capacitor bank can result in a negative se
quence voltage increase. The increase in motor losses
can be costly.
The BE1-47N should be applied to protect motor buses
from a open phase. It can also be applied to protect
critical individual motors, static and non-rotating loads
from the effects of negative sequence voltage.
A choice of time delay characteristics allows the relay to
respond in the desired manner for a wide variety of
transient and fault conditions.
The BE1-47N may also be used to provide over/
undervoltage protection. A separate time delay is uti
lized to prevent shutdown of equipment for minor volt
age dips and to permit sequential operation when the
relay is being used in a supervisory capacity.