GENERAL INFORMATION
INTRODUCTION
These instructions provide information concerning the operation and installation of BE1-25 Sync-Check
Relays. To accomplish this, the following is provided:
• Specifications
• Functional characteristics
• Mounting information
• Setting procedures and examples

Relays with a Type T power supply require a Contact Sensing Module, which comes supplied with its own
instructions, publication 9170206990.
These instructions may be used in place of all earlier editions. For change information, see Revision
History in the manual Introduction.
It is not the intention of these instructions to cover all details and variations in equipment, nor does this
manual provide data for every possible contingency regarding installation or operation. The availability
and design of all features and options are subject to modification without notice. Should further
information be required, contact Customer Service, Basler Electric Company, Highland, IL.
DESCRIPTION
The BE1-25 is a solid-state synchronism check relay designed to permit breaker closure when the
desired maximum phase angle conditions have held for a specified minimum time. The maximum
allowable phase angle and time delay requirements can be set on front panel thumbwheel switches. Five
voltage measuring options are available that identify significant line and bus voltage conditions, and this
information is used to influence the relay output.
APPLICATION
BE1-25 Sync-Check Relays are recommended for situations that require verification of synchronism prior
to closing a circuit breaker. Typical applications are:
• Paralleling a generator to a system.
• Reestablishing a connection between two parts of a power system.
• Supervising fast transfer schemes, where fast pickup and dropout of the phase measuring circuit
are required.
If optional voltage measuring circuits are incorporated, the BE1-25 can determine whether an input is live,
dead, or in an overvoltage state.
SYNC-CHECK FUNCTION
BE1-25 Sync-Check function measures the phase angle between single-phase voltages of line and bus.
Then sync-check verifies that this angle is less than the front panel PHASE ANGLE selector setting. If the
measured angle has met these criteria for the time period defined by the front panel TIME DELAY setting,
the SYNC output contact closes.
The allowable phase angle is adjustable over the range of 1 to 99 degrees. The time delay is adjustable
over either of two ranges: 1 to 99 cycles, 50/60 hertz (using the bus frequency as the reference), or 0.1
to 99 seconds (using the internal crystal controlled oscillator as the reference).
An optional target may be specified to indicate operation of the Sync-Check function.
CONTACT SENSING
To control operation of the relay, an input from the breaker auxiliary 52b contact is required to signal the
breaker status. If the breaker is open, the relay is enabled to perform its function. When the breaker
closes, the 52b input changes state and causes the relay to terminate its close signal.
Two configurations of the 52b contact sensing input are available to provide additional flexibility for the
protection circuit designer:
• Isolated contact sensing monitors a current supplied by the relay through an isolated contact.
• Non-isolated contact sensing monitors the presence of voltage at its input due to the closure of a
contact.
See Figure 4-10 for typical control circuit connections for each configuration. Also, see Figure 4-11 if a
Type T power supply has been selected.
VOLTAGE MONITOR OPTIONS
Mode Switches
Two Mode switches are located on the Voltage Monitor card. Mode Switch No. 1 serves the bus Voltage
Monitor function. Mode Switch No. 2 serves the line Voltage Monitor function. Mode switch positions are
as follows:
NORMAL Mode (Up) - allows measuring elements to establish live and dead reference levels for
the input level.
NOT-OV Mode (Down) - allows measuring elements to establish live and Not-Overvoltage
reference levels for the input level.
When a Mode Switch is in the NORMAL Mode position (Up), a dead level is defined as a monitored
voltage level below the DEAD reference setting. See Figure 1-1 for voltage monitor acceptance zones. A
live level is defined as a monitored voltage above the LIVE reference setting.
When a Mode Switch is in the NOT-OV Mode position (Down), a dead level is defined as a monitored
voltage less than the LIVE reference setting, and a live level is defined as a monitored voltage greater
than the LIVE reference setting, but less than the NOT-OV setting. (An input is considered over-voltage
when it exceeds the NOT-OV reference setting.)
It is permissible to operate the line input in either the same mode or a different mode than the bus input.
This flexibility allows the BE1-25 to be used, for example, to close a generator breaker onto a dead bus,
or to prevent closure if the generator and/or bus voltage is too high.
See Table 2-1. callout R, for a complete description and precautions on setting the Mode Switches. The
location of the switches is shown in Figure 2-2. Also, see Condition and Mode Switches in Section 5.
OTHER OPTIONS
Expandable Window
An expandable window (option 9 in the second position of the Style Number) is available to enable a local
operator (through a switch) or a remote dispatcher (through the supervisory control system) to expand the
preset phase angle window by a programmed ratio.
Under normal conditions, the phase angle setting is determined by the maximum angular difference that
has been calculated as suitable to meet the expected load flow of the total system. However, under
emergency conditions, the load flow throughout the system may result in excessive phase angle
separation across the opened breaker.
In order to reestablish load on a previously faulted line quickly, it may be necessary to expand the
allowable phase window. With this option, closing a contact input to the relay expands the preset phase
setting by a programmed multiple of 2 or 3 (according to the position of a jumper on the circuit card).
This option is not suggested for use in generator applications for the following reason: The phase angle
setting for a generator breaker is determined by the maximum phase difference that can be tolerated by
the generator when connected to the system. An excessive angle can result in excessive mechanical
forces in the generator and associated mountings.
Internal connections for the expandable window are shown in Figure 4-7; control circuit connections are
in Figures 4-10 and 4-11.
External Condition Switches
If a line and bus Voltage Monitor output is incorporated in the relay, the internal Condition Switches may
be functionally operated by remotely located external contacts. This capability is provided by Voltage
Monitor option 2-C, 2-U, or 2-V, but requires a voltage dropping Resistor Module to be mounted on the
relay back panel (see Figure 4-9).
Push-to-Energize Output Pushbuttons
Two PUSH-TO-ENERGIZE OUTPUT switches are available to provide a means of verifying external
output wiring without the inconvenience of having to test the entire relay. These optional switches are
provided for each isolated output function (Sync-Check, Auxiliary Sync-Check and Voltage Monitor), and
may be actuated by inserting a thin, non-conducting rod through access holes in the front panel. See
Figure 2-1 for location.