live level is defined as a monitored voltage above the LIVE reference setting.
When a Mode Switch is in the NOT-OV Mode position (Down), a dead level is defined as a monitored
voltage less than the LIVE reference setting, and a live level is defined as a monitored voltage greater
than the LIVE reference setting, but less than the NOT-OV setting. (An input is considered over-voltage
when it exceeds the NOT-OV reference setting.)
It is permissible to operate the line input in either the same mode or a different mode than the bus input.
This flexibility allows the BE1-25 to be used, for example, to close a generator breaker onto a dead bus,
or to prevent closure if the generator and/or bus voltage is too high.
See Table 2-1. callout R, for a complete description and precautions on setting the Mode Switches. The
location of the switches is shown in Figure 2-2. Also, see Condition and Mode Switches in Section 5.
OTHER OPTIONS
Expandable Window
An expandable window (option 9 in the second position of the Style Number) is available to enable a local
operator (through a switch) or a remote dispatcher (through the supervisory control system) to expand the
preset phase angle window by a programmed ratio.
Under normal conditions, the phase angle setting is determined by the maximum angular difference that
has been calculated as suitable to meet the expected load flow of the total system. However, under
emergency conditions, the load flow throughout the system may result in excessive phase angle
separation across the opened breaker.
In order to reestablish load on a previously faulted line quickly, it may be necessary to expand the
allowable phase window. With this option, closing a contact input to the relay expands the preset phase
setting by a programmed multiple of 2 or 3 (according to the position of a jumper on the circuit card).
This option is not suggested for use in generator applications for the following reason: The phase angle
setting for a generator breaker is determined by the maximum phase difference that can be tolerated by
the generator when connected to the system. An excessive angle can result in excessive mechanical
forces in the generator and associated mountings.
Internal connections for the expandable window are shown in Figure 4-7; control circuit connections are
in Figures 4-10 and 4-11.
External Condition Switches
If a line and bus Voltage Monitor output is incorporated in the relay, the internal Condition Switches may
be functionally operated by remotely located external contacts. This capability is provided by Voltage
Monitor option 2-C, 2-U, or 2-V, but requires a voltage dropping Resistor Module to be mounted on the
relay back panel (see Figure 4-9).
Push-to-Energize Output Pushbuttons
Two PUSH-TO-ENERGIZE OUTPUT switches are available to provide a means of verifying external
output wiring without the inconvenience of having to test the entire relay. These optional switches are
provided for each isolated output function (Sync-Check, Auxiliary Sync-Check and Voltage Monitor), and
may be actuated by inserting a thin, non-conducting rod through access holes in the front panel. See
Figure 2-1 for location.