Select Control Switch and Operate Control Switch pushbuttons provide a means to control the logic
switches.
The LCD has automatic priority logic to govern which metering values are displayed on the screen so that
when an operator approaches, the metering data of most interest is automatically displayed without
having to navigate the menu structure. Scrollable metering parameters are selected on the General
Settings, Front Panel HMI settings screen in BESTCOMSPlus.
Device Information
The version of the embedded software (firmware), serial number, and style number are available from the
front panel or the communication ports.
Three free-form fields (Device ID, Station ID, and User ID) can be used to enter information to identify the
BE1-11d. These fields are used by many of the reporting functions to identify the BE1-11d reporting the
information. Examples of BE1-11d identification field uses include station name, circuit number, relay
system, and purchase order.
Device Security
Security settings affect read and write access. Passwords provide access security for six distinct
functional access areas: Read, Control, Operator, Settings, Design, and Administrator. Each
username/password is assigned an access area with access to that area and each area below it. An
administrator password provides access to all six of the functional areas.
A second dimension of security is provided by the ability to restrict access for any of the access areas to
only specific communication ports. For example, you could set up security to deny access to control
commands through the Ethernet port.
Setting Groups
Four setting groups allow adaptive relaying to be implemented to optimize BE1-11d settings for various
operating conditions. Automatic and external logic can be employed to select the active setting group.
Clock
The clock is used by the logging functions to timestamp events. BE1-11d timekeeping can be self
managed by the internal clock or coordinated with an external source through a network or IRIG device.
A backup capacitor and additional battery backup are provided for the clock. During a loss of operating
power, the backup capacitor maintains timekeeping for up to 24 hours depending on conditions. As the
capacitor nears depletion, the backup battery takes over and maintains timekeeping. The backup battery
has a life expectancy of greater than five years depending on conditions.
IRIG
A standard unmodulated IRIG-B input receives time synchronization signals from a master clock.
Automatic daylight saving time compensation can be enabled and set for floating or fixed dates.
NTP (Network Time Protocol)
NTP synchronizes the real-time clock to network time servers through the Ethernet port. BESTCOMSPlus
is used to establish the priority of time reference sources available to the BE1-11d, IRIG-B, NTP, DNP,
and RTC (real-time clock). The NTP address is set using BESTCOMSPlus.
Communications
Three independent communication ports provide access to all BE1-11d functions. A USB (universal serial
bus) port is located on the front panel, a two-wire RS-485 port is located on the rear panel, and an
optional Ethernet port is located on the rear panel. The RS-485 and Ethernet ports are electrically
isolated.
Modbus® and DNP3 protocols are optionally available for the RS-485 or Ethernet communication port.
The IEC 61850 protocol is optionally available for the Ethernet port when RS-485 option is N (None).
Separate instruction manuals cover each available protocol. Consult the product bulletin or Basler Electric
for availability of these options and instruction manuals. Modbus sessions can be operated
simultaneously over the Ethernet and RS-485 ports.
System Parameters
All sensing is performed using an IT-D isolation module. Each IT-D isolation module includes two
channels that are capable of sensing either dc current or dc voltage. The dc system current is sensed
using an appropriately scaled 25. 50. 75. or 100-millivolt nominal metering shunt. DC voltages are sensed
by direct connection for nominal levels up to 1.500 Vdc. The BE1-11d can utilize two IT-D modules to
sense a single dc current and up to three dc voltages.