and synchronizing/load sharing modules. When the AVC receives a positive voltage
(terminal 2 positive, terminal 3 negative) at the accessory input, the regulation
setpoint decreases. A negative voltage (terminal 2 negative, terminal 3 positive)
at the accessory input increases the regulation setpoint. Figure 9 illustrates
interconnection of the AVC accessory input with an SCP 250 Var/Power Factor
Controller and an EL 200 Minimum/Maximum Excitation Limiter.
When using an external biasing device, ensure that it is configured properly for
use with the AVC63-12 or AVC125-10.