The AO845/AO845A Analog Output Module for single or redundant
applications has 8 unipolar analog output channels. The module
performs self-diagnostic cyclically. Module diagnostics include:
External Channel Error is reported (only reported on active
channels) if the process power supply that supply voltage to
output circuitry is too low, or the output current is less than the
output set value and the output set value > 1 mA (open circuit).
Internal Channel Error is reported if the output circuit can not
give the right current value. In a redundant pair the module will be
commanded to error state by the ModuleBus master.
Module Error is reported in case of Output Transistor Error, Short
Circuit, Checksum Error, Internal Power Supply Error, Status Link
Error, Watchdog or Wrong OSP behavior.
Features and benefits
• 8 channels of 4...20 mA
• For single or redundant applications
• 1 group of 8 channels isolated from ground
• Analog inputs are short circuit secured to ZP or +24 V
• HART pass-through communication
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved