INTRODUCTION
The AEC63-7 voltage regulator is designed for use on low
voltage, 50/60 Hz brushless generators. Regulator
features include frequency compensation, overexcitation
detection and output, a solid-state buildup circuit, and
internal noise suppression.

FUNCTIONAL DESCRIPTION
Frequency Compensation
The frequency compensation characteristic of Figure 1 is
used to improve system load pickup performance by
restraining voltage recovery until frequency has also
started to recover. The regulator is shipped from the
factory set at a 47-Hz corner frequency for 50 Hz systems.
For 60 Hz systems, a 57-Hz corner frequency is achieved
by moving the jumper wire from the 50 and HZ terminals
to the 60 and HZ terminals.
Overexcitation Time Delay
If the regulator output voltage exceeds 65 Vdc ±2 Vdc, the
regulator automatically makes a connection across
terminals A1 and A2 via an optically-isolated triac device.
This occurs after a time delay which is inversely
proportional to the magnitude of the regulator output
overvoltage condition up to approximately 105 Vdc ±5 Vdc
(see Figure 2). Beyond this point, the field voltage is
removed at a much faster rate. To avoid tripping due to
the voltage provided by a separate current boost circuit,
voltage measurement excludes any additional boost
voltage term. The overexcitation circuit is reset by
reducing the regulator input voltage to less than its buildup
value for 5 seconds.
This feature is designed to protect the generator and
regulator by allowing disconnection of the overloaded
part(s) of the system. Should the regulator be allowed to
run in excess of its rated current for any extended period
of time after the protection output closes, failure of the
recommended supply fuse will occur, but regulator
damage may also take place.
Overexcitation Shutdown
Overexcitation detection provides a single-pole solid-state
contact closure across terminals A1 and A2. should the
regulator output voltage exceed 65 Vdc ±2 Vdc for a
sufficient time. For voltage above 105 Vdc ±5 Vdc, there is
a second (shorter) inverse time curve. The total inverse
time delay curve is shown in Figure 2.
After the overexcitation solid-state contact has been
made, the regulator overexcitation circuit can be reset by
decreasing the supply voltage on terminals 3 and 4 to less
than 6 Vac for a minimum of 2 seconds. This may be
accomplished by stopping the prime mover or interrupting
the regulator input by means of a reset switch. In cases
where the generator is operating in parallel mode, it may
not be desirable to allow the regulator alone to shut down
which may cause the generator to be motored. However,
continuous operation at output currents greater than the
continuous rating after the overexcitation contact has been
made may result in failure of the ac supply fuse or may
eventually cause regulator failure. If this kind of operation
will take place, an alternative external means should be
employed to protect the system.
A1 and A2 are optically isolated and floating. Any supply,
12 to 250 Vac or dc may be used, provided that current is
limited to 150 mA. Use of a dc supply to terminals A1 and
A2 will cause the solid-state device to latch after tripping.
In this case, the supply must also be removed to unlatch
the device.
Current Boost Logic
The Current Boost Logic, provided at terminals CB+ and
CB–, allows the regulator to enable and disable an
external Current Boost System. The interface is designed
to operate with Basler Current Boost models CBS305 and
CBS212A.
If the sensing voltage drops about 10% below the voltage
setpoint, then the Current Boost Logic will enable the
Current Boost System. Once the sensing voltage
increases to about 5% below the voltage setpoint, the
Current Boost System will be disabled.
When the Current Boost interface is not required, then no
connections should be made at terminals CB+ and CB–.
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved