Application
The differential function offers a high sensitivity for
low-level internal faults. The unique and innovative
sensitive differential protection feature of the
RET670 provides the best possible coverage for
winding internal turn-to-turn faults, based on well
known theory of symmetrical components .
Low impedance restricted earth-fault protection
functions are available as complimentary sensitive
and fast main protection against winding earth
faults. This function includes a directional zero
sequence current criterion for additional security.
Additionally a high impedance differential function
is available.
It can be used as restricted earth
fault or, as three functions are included, also as
differential protection on autotransformers, as
differential protection for a tertiary connected
reactor, as T-differential protection for the
transformer feeder in a mesh-corner or ring
arrangement, as tertiary bus protection and so on.
Tripping from Pressure relief/Buchholz and
temperature devices can be done through the
transformer IED where pulsing, lock-out contact
output and so on, is performed. The binary inputs
are heavily stabilized against disturbance to
prevent incorrect operations at for example, dc
system capacitive discharges or DC earth faults.
Distance protection functionality for phase-to
phase and/or phase-to-earth faults is available as
back-up protection for faults within the
transformer and in the connected power system.