Construction
Hardware
The REG216 device consists of two main components, which are physically separated from each other and connected by standard prefabricated shielded cables
Connected by standard prefabricated shielded cables:
- The main system interface (CT, PT and auxiliary relays), which provides DC isolation and EMI barriers.
Isolation and EMI barrier
- Parallel bus and associated electronic units (e.g. analog inputs and data processors / for signal conditioning and processing).
The complete protection scheme consists of a relatively small number of hardware modules, allowing subsequent expansion of the electronic units and interfaces. Each device frame provides 21 rack spaces.
All hardware can be housed in a single compartment, which provides further shielding against inductive interference and physical protection against dust, etc.
All hardware can be accommodated in a single compartment, which provides further shielding from inductive interference and physical protection from dust.
The REG216 is available in 17 predefined rack configurations with a limited number of I/Os, but is equipped with the same SW library as the classic system.
Protective relays for other functions are not part of the EG216 and can be installed in compartments and interconnected with the REG216 accordingly.
Interfaces to the main system
The following modular components provide the interface between the REG216 and the power system.
Input transformer assembly
216GW62 This assembly is used to adjust the signal level and to isolate the primary system CT and PT circuits from the electronic circuits of the protective devices.
One PT and two CTs are available to meet different accuracy and dynamic performance requirements.
Up to 12 transformers can be accommodated, selected according to application requirements. Up to four components, i.e. 48 inputs, can be used.
Auxiliary relay and optocoupler assembly 216GD61a
This assembly is for use with the REG216 version. It provides eight trip relays,
Each relay has powerful potential-free trip contacts (with surge circuit), 16 auxiliary relays and 16 optocouplers.
relays and 16 optocoupler input circuits. Up to four assemblies are available.
Input Auxiliary Relay Assembly 216GE61
Up to 16 auxiliary relays to provide full potential isolation for digital input signals.
Output Auxiliary Relay Assembly 216GA61
Up to 16 auxiliary relays providing full potential separation for digital output signals (two contacts per signal).
Trip Auxiliary Relay Assembly 216GA62
Provides up to 8 powerful potential-free trip contacts and circuits that provide high-speed operation (surge circuits) and reduced consumption after operation (economy circuits).
The Trip Auxiliary Relay Assembly is available with an optional trip logic diode matrix for direct coupling of external signals.
Matrix for direct coupling of external signals The REG216 can also read and process external signals via digital inputs.
Different trip circuit monitoring arrangements for use with output unit 216DB61 and input auxiliary relay assembly 216GE61 are available