8205-TI-IS
• 8 input channels
• Intrinsically safe field circuits
• Thermocouple and mV
• Cold junction compensation
(internal or remote)
• Built-in thermocouple linearisation
• Channels independently configurable
• Open-circuit field wiring detection
MODULE SPECIFICATION
See also System Specification
INPUTS
Number of channels
• 8
THC inputs
• B,E,J,K,N,R,S or T to EN 60584-1: 1995;
• W3 and W5 to ASTM E 988-96
• Russian K and Russian L to rOCT 3044-84
• User definable linearisation table, NOTE 1
Temperature drift
• < ± 0.003% of span/°C
Cold junction compensation error*
• < ± 1°C (– 40 to + 70°C)
Resolution
• 16 bits
Common mode rejection
• >87 dB @ 50/60 Hz
Series mode rejection
• >50 dB @ 50/60 Hz
Common mode voltage between channels
• ± 5 V (max.)
Absolute maximum input voltage
• ± 30 V
Isolation (any channel to Railbus)
• 60 V peak
CONFIGURABLE PARAMETERS
Sensor type
• User selectable
Alarms
• High and low
Input dead zone
• User defined value
Selectable input filtering
• Off / 2 reading avgerage / running avgerage
Drive on open circuit fault
• Disabled / upscale / downscale
Channel status
• Active / Inactive
Cold junction compensation
• Enable / disable / channel number
RESPONSE TIME
Analog signal change to availability on Railbus
• 600 ms (max.)
SAFETY
Field wiring protection
• [EEx ia] IIC
Safety Description (each channel)
• Channels 1. 2. 3. 4. 7 and 8. wired as separate
IS circuits – Uo = 16.4 V, Io = 79 mA, Po = 0.33 W
Channels 5 and 6. wired as separate IS circuits –
Uo = 1 V, Io = 1.1 mA, Po = 0.3 mW
(Input terminals are equivalent to non-energy storing apparatus)
FM entity parameters
• Channels 1. 2. 3. 4. 7 and 8. wired as separate IS
circuits – Voc = 16.4 V, Isc = 63.7 mA, Po = 131mW
• Channels 5 and 6. wired as separate IS circuits –
Uo = 1 V, Io = 1 mA, Po = 0.25 mW