Functions
The scope of functions provided by the Freelance
system corresponds to the basic supply defined in
IEC 611 1- , in addition to numerous other high
performance, industry-proven functions and function
blocks. They are accommodated in a function block
library and can be supplemented by user-specific
function blocks. While designing the station and
during configuration, the processing capacity and
speed of the process station can be easily adapted
to the demands of the automation task. Program
execution in the process station is based on a task
oriented, real-time multitasking operating system,
leading to a flexible strategy for processing programs.
Different modes are available for task execution:
• Cyclical processing with cycle times from 5 ms upwards
• Fastest-possible processing (PLC mode)

Along with the user tasks, system tasks – in which
functions can also be processed – are automatically
made available. These tasks are executed once in
case of the following events:
- RUN
- STOP
- COLD START
- WARM START (voltage restored)
- REDUNDANCY TOGGLE- ERROR
Up to eight cyclic user tasks and one PLC mode task
can be configured in a process station.
Fieldbus modules
The AC 800F uses the fieldbus modules to collect
and process real-time and diagnostic data. Up to
four fieldbus modules can be mounted into one AC 800F.
The fieldbus modules have the following tasks and
characteristics:
• Electrical isolation between the process and system
• Status LEDs for the module status
• Independent fault detection and fault signaling
• Connection of the fieldbus lines
Ethernet modules
Process stations and the operator and engineering
level in the Freelance 800F system communicate with
each other via Ethernet.
Intelligent linking devices
As the AC 800F possesses the high-speed connec
tion of both PROFIBUS (PROFIBUS DP) and FOUN
DATION Fieldbus (FF-HSE), the slower buses of the
two fieldbus technologies (PROFIBUS PA and FF-H1)
can be connected using intelligent linking devices.
These devices allow to connect several slow buses
to one fast bus, with the advantage that a lot more
field devices can be connected to an AC 800F sta
tion than when the slow fieldbuses are connected directly.
LD 800P PRoFIbuS DP/PA Linking Device
LD 800P is needed to connect PROFIBUS DP to
PROFIBUS PA. The LD 800P Linking Device converts
the physical bus characteristics of the RS 485 inter
face for the PROFIBUS DP into PROFIBUS PA physi
cal bus characteristics according to IEC 61158- ,
enables connected PROFIBUS PA devices to be
supplied with power via the bus, and additionally
allows use in intrinisically safe areas.