Description
The 2585 16-Point TTL Input Module accepts sixteen
TTL driven inputs to the CTI 2500 SeriesTM or
Simatic® 505 Series I/O base. The inputs are
isolated channel-to-channel.
The 2585 has an input voltage range from 2.6 to 28
VDC; therefore, the inputs may be driven by CMOS
and open collector transistor devices.

Features
• CTI 2500 Series and Simatic 505 base format
• 500 V channel-to-channel isolation
• 1500 V channel-to-PLC backplane isolation
Specifications
Inputs per module: 16
Isolation:
500 VDC channel-to-channel
1500 VDC channel-to-backplane
Input Voltage:
2.6 to 28 VDC
TTL OFF <0.8 VDC TTL ON > 2.6 VDC
1500 VDC channel-to-backplane
Input Current:
20 mA max. per circuit (0.5 mA @ 2.6 VDC)
Isolation:1500 VDC channel-to-backplane
Turn ON Time: Approx. 1 mSec nominal
Turn OFF Time: Approx. 2 mSec nominal PLC
Reporting: X or WX (jumper selectable)
Wire gauge: 14-22 AWG removable connectors
Backplane power: 1.4 Watts (all outputs active)
Module size: Single-wide
Blown fuse indication: Front panel LED
Shipping Weight: 1.5 lb. (0.68 Kg)
Additional Product Information:
On CTI’s Website you find will links to the 2500
Series Std Environmental Specifications and the UL
Agency Certificates of Compliance .
Word and Discrete Mode
The 2585 may operate as a 16 Bit Word Input Module or as a 16 Dis
crete Input Module. By setting JP1 in Word Mode and using Workshop
to configure I/O the 2585 will look like a standard WX input module; for
example WX1-WX8.
NOTE: The 2585 will be mapped as the first WX address (i.e. WX1). In
Word Mode Channel 1 corresponds to bit 16 or LSB and Channel 16
corresponds to Bit 1 or MSB.
Note:
If the address line is blank or erroneous, re
check the module to ensure that it is firmly
seated in the slots. Generate the PLC I/O
configuration chart again. If the address
line is still incorrect, contact your local dis
tributor or CTI at 1-800-537-8398 for fur
ther assistance.
Changing Operating Modes
Any time the operating mode of the 2585 is
changed with JP1. the module must be con
figured in the PLC. Failure to do so may
cause unpredictable operation due to the
fact that the PLC uses different methods of
addressing discrete modules from word
modules.