Easy Asset Supervision
• Permanently mounts on a single transformer oil
valve. No extra piping or pump required
• "Composite gas" sensor responds 100% to
Hydrogen (general fault gas) and is also sensitive
to Carbon Monoxide (overheated paper)
Acetylene (arcing) and Ethylene (overheated oil)
thus covering main failure root causes
• "Hydrogen only" gas sensor is simpler and
responds 100% to Hydrogen gas only, the
general fault gas
Configurable Alarms
• An alarm is raised when an abnormal level of
fault gas is detected
• Two alarm levels (one for Alert and one for Alarm)
can be set to show increasing severity
• Alarms can be set on gas ppm levels or on gas
rate of change (ROC) over an hour or a day
• Automatic self-test every 15 days will trigger
service alarm if it detects a fault, including power
failure, oil valve closed, sensor or battery needing
replacement
Human Interface
• Backlit LCD display of gas information
• Keypad to stop unit and acknowledge alarms
• Compatibility with GE’s acclaimed Perception™
software to download, trend and analyze
transformer data
Mark IV Improvements
• Completely overhauled with improved sensor
durability, new electronic boards and power
supply to make it RoHS compliant while
increasing device reliability and capabilities
• Local USB port to replace the RS-232 port no
longer found on most field laptops
• Digital output of registers using Modbus®
protocol communication over isolated RS-485
Controllers
The Hydran 201Ti can be connected to optional controllers to facilitate
communication with multiple units and create a local network.
• The Ci-1 controller is a one channel controller that replicates some of
the human interface functions (gas value display, alarm buttons). This is
ideal when the 201Ti is mounted out of reach on an upper valve of the
transformer. It also brings down the alarm relay contacts and the analogue
output for easier wiring.
• The Ci-C controller receives the gas ppm data from up to four 201Ti,
providing a single communication point for all four monitors. It has no
alarm relay or analogue output. This is ideal when protecting 3 single phase
transformers + 1 spare.
It is possible to “daisy-chain” up to 32 controllers or 201Ti through their RS-485
port. The maximum chain distance (all cables added up) is 1200m (4000ft). All
the 201Ti connected to any of the daisy-chained controllers can be accessed
through any controller in the local network, thus facilitating communication by
only having to fit one RS-232 modem for example.