Overview
REF601 is a dedicated feeder protection relay, intended for the protection
and control of utility substations and industrial power systems.
The relay is compatible with the Rogowski coil sensor for current measurement.
The feeder protection relay REF601 is designed to unleash the advantages of
current sensors for protection and control in medium voltage applications.
The REF601 features compact size and ease of use.
The features include:
Sensor input for phase current measurement
Earth current measurement internally or externally through CBCT
Three-stage overcurrent protection
Two-stage earth-fault protection
Inrush detection for stability during transformer charging
Local and remote control of circuit breaker
Trip Circuit Supervision
Lockout function
100 event logs
Two analogue fault records
Non-resettable trip counter
On-line current measurements in primary value
Comprehensive local HMI
Universal auxiliary supply
Compact design suitable for circuit breaker or panel mounting
Optional MODBUS RTU communication
Non-volatile memory for setting and fault records
Self-supervision
User selectable rated frequency 50 / 60 Hz
Operation Functionality
Relay functions
REF601 offers pre-configured functionality which facilitates easy and fast
commissioning of switchgear. To emphasize the relay’s simplicity of usage,
only application specific parameters needs to set within the relay’s intended area of application.
The settings can be changed by LHMI (local human-machin interface) or
through optional communication interface MODBUS master with setting capability.
The relay offers protection, control, measurement and condition monitoring functionality.
The table indicates the Functions supported by the IED
Optional function
Communication on MODBUS RTU Protocol
Other Functions
Self Supervision
The IED is provided with an extensive self-supervision system which
continuously supervises the software and the electronics.
It handles runtime fault situations and informs the user about an existing fault via the LHMI.
When in an IED internal fault is detected, the green Ready LED ceases to
glow and the self-supervision output contact is activated. Internal fault
indications have the highest priority on the LHMI. None of the other
LHMI indications can override the internal fault indication. An indication
about the fault is also shown as a message on the LHMI. The text IRF with
an additional text message, a code is shown to indicate the fault type.
The user can try to eliminate the fault by restarting the IED. If the fault is
still found, the IED stays in internal fault mode. All other output contacts
are released and locked for the internal fault.
The self-supervision signal output operates on the closed circuit principle.
Under normal conditions the relay is energized and the contact gap 5-6 in
connector XK2 is closed. If the auxiliary power supply fail or an internal
fault is detected, the contact gap 5-6 is opened.