General Description
This module mounts into 1746 I/O chassis for use with SLC 500 fixed
and modular systems. The module stores digitally converted
thermocouple/mV analog data in its image table for retrieval by all
fixed and modular SLC 500 processors. The module supports
connections from any combination of up to eight thermocouple/mV
analog sensors.
Input Ranges
The following tables define thermocouple types and associated
temperature ranges and the millivolt analog input signal ranges that
each of the module’s input channels support. To determine the
practical temperature range of your thermocouple, refer to the
specifications in Appendix A.
Each input channel is individually configured for a specific input
device, and provides open-circuit, over-range, and under-range
detection and indication.
Hardware Features
The module fits into any single slot for I/O modules in either an SLC
500 modular system or an SLC 500 fixed system expansion chassis
(1746-A2), except the zero slot which is reserved for the processor. It
is a Class 1 module using 8 input words and 8 output words.(2)
The module contains a removable terminal block providing
connections for eight thermocouple and/or analog input devices. On
the terminal block are two cold-junction compensation (CJC) sensors
that compensate for the cold junction at ambient temperature. It
should also be noted there are no output channels on the module.
Configure the module with software rather than with jumpers or
switches.
IMPORTANT
There is a jumper (JP1) on the circuit board. The
module is shipped with the jumper in the up
position as illustrated below. Do not change the
position of JP1. The jumper is used for test purposes
only.
Hardware Features
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com