Overview
This chapter describes the four-channel 1746-NR4 RTD/Resistance
Input Module and explains how the SLC controller gathers RTD
(Resistance Temperature Detector) temperature or resistance-initiated
analog input from the module.Included is:
• a general description of the module’s hardware and software features.
• an overview of system operation.
For the rest of the manual, the 1746-NR4 RTD/Resistance Input
Module is referred to as simply the RTD module.
Description
The RTD module receives and stores digitally converted analog data
from RTD units or other resistance inputs such as potentiometers into
its image table for retrieval by all fixed and modular SLC 500
processors. An RTD module consists of a temperature-sensing element
connected by two, three, or four wires that provide input to the RTD
module. The module supports connections from any combination of
up to four RTD units of various types (for example: platinum, nickel,
copper, or nickel-iron) or other resistance inputs.
The RTD module supplies a small current to each RTD unit connected
to the module inputs (up to 4 input channels). The module provides
on-board scaling and converts RTD unit input to temperature (°C, °F)
or reports resistance input in ohms.
Each input channel is individually configurable for a specific input
device. Broken sensor detection (open- or short-circuit) is provided
for each input channel. In addition, the module provides indication if
the input signal is out-of-range.
System Operation
The RTD module has three operational states.
• Cycle power
• Module operation
• Error (module error and channel error)
Cycle Power
When you cycle the module’s power, the RTD module checks its
internal circuits, memory, and basic functions via hardware and
software diagnostics. During this time the module status LED indicator
remains off. If no faults are found during the diagnostics, the module
status LED indicator is on.
After the checks are complete, the RTD module waits for valid
channel configuration data from your SLC ladder logic program
(channel status LED indicators off). After configuration data is written
to one or more channel configuration words and their channel enable
bits are set by the user program, the channel status LED indicators go
on and the module continuously converts the RTD or resistance input
to a value within the range you selected for the enabled channels. The
module is now operating in its normal state.
Each time a channel is read by the module, that data value is tested by
the module for a fault condition, for example, open circuit, short
circuit, over range, and under range. If such a condition is detected, a
unique bit is set in the channel status word and the channel status
LED indicator blinks, indicating a channel error condition.
The SLC processor reads the converted RTD or resistance data from
the module at the end of the program scan or when commanded by
the ladder program. The processor and RTD module determine that
the backplane data transfer was made without error and the data is
used in your ladder program.