Basler BE1‑FLEX Communication Integration Manual
Product Overview
BE1‑FLEX from Basler Electric is a multifunctional protection, automation and control Intelligent Electronic Device (IED) for power‑utility substations and industrial power systems. This document —Communication Integration Manual Revision‑B, Publication No.9579200991 (July‑2023) — covers exclusively communication configuration instead of protection element settings.
BE1‑FLEX supports four major industrial communication protocols:Modbus, DNP3. Synchrophasor(IEEE C37.118.2), IEC 61850. Protocol availability depends on installed software license: Protocol‑Package‑01 enables Modbus & DNP3; Protocol‑Package‑02 adds full IEC 61850 functionality.
Hardware communication interfaces include RS‑485 serial port, copper Ethernet (10/100/1000Base‑T) and optional 100Base‑FX LC fiber‑optic Ethernet. All communication parameters are configured within the Windows‑basedBESTCOMSPlus configuration software.
Important hardware note: Non‑volatile memory inside BE1‑FLEX has maximum endurance rating20 TBW (Terabytes‑Written). Frequent repeated register‑writes over communication will consume flash lifespan. Use Auto‑Save group‑save feature to reduce write cycles.

Supported Communication Protocols
1. Modbus Communication
BE1‑FLEX always acts asModbus Server (Slave) for client‑master devices such as SCADA, PLC and HMI.
- Transport options: Modbus‑RTU over RS‑485 serial; Modbus‑TCP over Ethernet (TCP port 502).
- Fully customizable Modbus Map inside BESTCOMSPlus:
- Empty map by default, use `Generate` for auto‑populate signal list.
- Supports manual edit of starting holding‑register address, add / delete signal entries.
- Import / export mapping file with `.bstm` extension; export map to CSV for documentation.
- Special function registers: security login/logout registers, SBO (Select‑Before‑Operate) control registers for virtual switches & breaker control, manual Save‑Key register for flash persistence.
- Supported data types: BoolType, Int32. Uint32. Float32. Double64. String.
- Implemented Modbus function‑codes: 03. 06. 08. 16.
2. DNP3 Communication
BE1‑FLEX operates asDNP3 Level‑2 Outstation.
- Physical media: RS‑485 serial or Ethernet (TCP / UDP).
- DNP Map configuration: auto‑generate signal list, configure dead‑band, scaling‑factor, event‑class assignment for binary & analog points.
- Mapping can be imported / exported with `.bstd` file extension, exportable to CSV.
- Main capabilities: binary inputs / outputs, analog measurements, time‑tagged event reporting, unsolicited responses, Select‑Operate / Direct‑Operate breaker control, time‑synchronization.
- Manual includes full DNP3 Device‑Profile and Implementation‑Table for third‑party master‑station integration.
3. Synchrophasor (PMU IEEE C37.118.2)
- Compliant withIEEE C37.118.2 synchrophasor standard.
- Configured under BESTCOMSPlus `Circuit Summary > Synchrophasor Configuration`.
- Publish 3‑phase voltage & current phasor magnitude / angle data.
- Data output: UDP multicast address `239.253.10.1` port 4713; control‑command unicast port 4712. User‑configurable reporting‑rate and PMU‑ID code.
4. IEC 61850 Communication (Protocol‑Package‑02 license required, Ethernet‑only)
BE1‑FLEX functions as an IEC 61850 IED server.GOOSE peer‑to‑peer messaging and MMS reporting are supported; SV Sampled‑Values is NOT supported.
1. SCL file workflow:
- ICD (IED Capability Description), CID (configured IED file), SCD (Substation‑Configuration‑Description), SSD system specification.
- Import & export SCD / CID files inside BESTCOMSPlus. GOOSE inputs / outputs map to internal BESTlogicPlus programmable logic.
2. Core services:
- MMS: BRCB buffered report control blocks, URCB un‑buffered report blocks; file transfer for COMTRADE fault‑records, SOE sequence‑of‑events, load‑profile logs.
- GOOSE: Up to four independent GOOSE publish/subscribe blocks for fast inter‑IED bay‑level interlocking.
3. Rich logical‑node library: MMXU measurements, XCBR breaker, PIOC instantaneous overcurrent, PTOC time‑over‑current, PTUV under‑voltage, PTOV over‑voltage, RBRF breaker‑failure, RREC auto‑reclosing etc.
4. Time‑synchronization: SNTP and IRIG‑B timing input.
5. Communication‑fault alarm logic blocks available for BESTlogicPlus logic programming.
6. Complete conformance documents: MICS, PICS, PIXIT included in manual for compliance testing.
Software Tool: BESTCOMSPlus
BESTCOMSPlus for Windows is the unified configuration platform:
- Set all protocol parameters, edit Modbus / DNP point‑maps.
- Import / export IEC 61850 SCL configuration files.
- Configure BESTlogicPlus programmable logic for GOOSE signal mapping and custom logic.
Typical Application Scenarios
- Substation protection‑and‑control IED integration with SCADA / RTU / DCS
- Legacy‑system retrofit: Modbus & DNP3 connection to existing plant SCADA
- Digital‑substation deployment using IEC 61850 GOOSE & MMS
- Wide‑area monitoring via IEEE C37.118 synchrophasor PMU data
Frequently Asked Questions
Q: Which license enables IEC 61850 on BE1‑FLEX?
A: Protocol‑Package‑02; Package‑01 only includes Modbus and DNP3. IEC 61850 runs only over Ethernet interface, RS‑485 serial port does NOT support IEC 61850.
Q: Can BE1‑FLEX act as Modbus master?
A: No, BE1‑FLEX is strictly Modbus server / slave. Your SCADA or PLC must be Modbus‑client / master.
Q: Does BE1‑FLEX IEC 61850 support SV sampled‑values?
A: No. It supports MMS reporting and GOOSE peer‑to‑peer, SV sampled‑value service is not implemented.
Q: What is the flash‑memory limitation for communication writes?
A: Non‑volatile memory maximum endurance rating is20 TBW. Always use Auto‑Save setting to group register‑writes and reduce flash wear.