4. Time‑synchronization: SNTP and IRIG‑B timing input.
5. Communication‑fault alarm logic blocks available for BESTlogicPlus logic programming.
6. Complete conformance documents: MICS, PICS, PIXIT included in manual for compliance testing.
Software Tool: BESTCOMSPlus
BESTCOMSPlus for Windows is the unified configuration platform:
- Set all protocol parameters, edit Modbus / DNP point‑maps.
- Import / export IEC 61850 SCL configuration files.
- Configure BESTlogicPlus programmable logic for GOOSE signal mapping and custom logic.
Typical Application Scenarios
- Substation protection‑and‑control IED integration with SCADA / RTU / DCS
- Legacy‑system retrofit: Modbus & DNP3 connection to existing plant SCADA
- Digital‑substation deployment using IEC 61850 GOOSE & MMS
- Wide‑area monitoring via IEEE C37.118 synchrophasor PMU data
Frequently Asked Questions
Q: Which license enables IEC 61850 on BE1‑FLEX?
A: Protocol‑Package‑02; Package‑01 only includes Modbus and DNP3. IEC 61850 runs only over Ethernet interface, RS‑485 serial port does NOT support IEC 61850.
Q: Can BE1‑FLEX act as Modbus master?
A: No, BE1‑FLEX is strictly Modbus server / slave. Your SCADA or PLC must be Modbus‑client / master.
Q: Does BE1‑FLEX IEC 61850 support SV sampled‑values?
A: No. It supports MMS reporting and GOOSE peer‑to‑peer, SV sampled‑value service is not implemented.
Q: What is the flash‑memory limitation for communication writes?
A: Non‑volatile memory maximum endurance rating is20 TBW. Always use Auto‑Save setting to group register‑writes and reduce flash wear.