- Discrete Inputs 19 configurable contact inputs (16 additional contact inputs can be added using LinkNet HT)
- Analogue Inputs 8 configurable 4-20 mA (16 inputs or 8 RTD inputs can be added using LinkNet HT)
Outputs
- Valve/actuator driver: 2 actuator outputs, 4-20 mA or 20-200 mA
- Discrete Outputs:
- 7 configurable relay outputs (16 discrete outputs can be added using the LinkNet HT module)
- Analogue Outputs 6 programmable 4-20 mA outputs (4 inputs can be added using the LinkNet HT module)
Communications
- Ethernet 3 ports (Modbus TCP or OPC)
- Serial 1 port (ASCII or RTU, RS-232 or RS-485)
- CAN: 4 ports, supports LinkNet HT, VariStroke, and power management devices
Operating Conditions
- Ambient air temperature: -25 to +65C
- Humidity Lloyd's ENV2 Test #1
- Dry heat Lloyd's ENV3
- Salt Spray: US MIL-STD-810. Method 509.2 proc. 1
- Shock: US MIL-STD-810C, Method 516.2-1 proc. 1B
- Vibration Lloyd's ENV2 Test #1
- Resistance to particulate contamination IEC 60664-1 Class 2
- IEC 60068-2-60 part 2.60 methods 1 and 4
- Resistance to gaseous contamination: coating is resistant to NO2. CO2. SO2 and H2S.
- Battelle Laboratories Class III (IEC 60721-3-3 Categories 3C1 and 3C2)