Functions
The 2301E-J has speed control, load control, equal speed/no load transfer, and fuel limiter functions.
Speed Control Function
- Rated speed range of 400-3600 rpm
- Constant speed speed control
- kW Reduced speed control
- Simple derating control is selectable (when selected, the load control function is not available)
- Idling/rated speed switching by discrete input signal
- Speed reference up/down using discrete input signals
- Fast synchronisation using analogue speed bias signal from synchroniser
- (Optional) Speed reference manipulation function using remote analogue signal
- Single point control gain setting (optional)
- A control gain curve consisting of 5 points with 4 ramps can be mapped to the engine to change gain under various operating conditions.
- Dual power function to switch control power according to engine load
Load control function
- Automatic isochronous load sharing function (including soft load handling from the generator breaker close to the start of automatic load sharing)
- kW Initial loading function after the generator breaker is closed in down operation.
- Automatic soft unloading function (generator breaker open output signal is unloading trip level)
- Asynchronous base load operation (optional remote load setting function)
- kW descending operation (remote load setting function via remote speed setting signal)
- Generator load operation using the speed down function. (The load control function is not applicable to speed drop operation).
Fuel Limiter Function
The 2301E-J has the following six fuel limiter functions:
- Start-up fuel limiter (including lower limit, upper limit, and slope from lower limit to upper limit)
- Maximum Fuel Limiter
- Torque limiter (5 points and 4 ramps)
- Boost Fuel Limiter (optional) (5 points and 4 ramps)
- Discrete Input Fuel Limiter
- Fuel limit is cancelled by discrete input signal
Equal Speed/Idle Switching Function
- Isochronous/idle switching by discrete input signal
- Trouble-free switching from isochronous operation to kW down operation
- Load ramp from kW load drop level when connected in parallel with the utility to isochronous load sharing level when connected in parallel
Isochronous base load operation
- Base load set point raise/lower function with discrete inputs
- Generator kW load remains constant regardless of utility frequency
- Base load set point raised/lowered by analogue remote signal