specifications.
Tricon modules are field-replaceable units consisting of an electronic assembly housed in a
metal spine. Each module has a protective cover that ensures no components or circuits are
exposed even when a module is removed from the chassis. Offset backplane connectors make it
impossible to plug a module in upside down, and keys on each module prevent the insertion of
modules into incorrect slots. The Tricon controller supports digital and analog input and output
points, as well as pulse and thermocouple inputs and multiple communication protocols.
Tricon Controller Chassis
A Tricon controller can include a maximum of 15 chassis, housing any appropriate combination
of input, output, communication, interface, and hot-spare modules. There are three types of
chassis: Main, Expansion, and RXM.
• The Main Chassis houses the Main Processor modules and I/O modules. The Model
8110 Main Chassis houses up to six slot sets of I/O modules and the Model 8120E
Enhanced Performance Main Chassis houses up to five sets of I/O modules. The I/O
modules in a chassis are connected via I/O expansion bus ports that are triplicated RS
485 bi-directional communication ports.
• An Expansion Chassis (chassis 2 to 15) houses up to eight slot sets of I/O modules and
HART™ Interface Modules. The Expansion Chassis connects to the Main Chassis by
means of a triplicated RS-485 bi-directional communication port. Generally, the last
Expansion Chassis must be located no more than 100 feet (30 meters) from the Main
Chassis or an RXM Chassis.
• An RXM Chassis houses a Primary or Remote RXM Module set and six slot sets of I/O
modules. An RXM Chassis enables a system to extend to remote locations up to 7.5
miles (12 kilometers) from the Main Chassis, using SRXM modules.