The Enhanced Micro TDC3000 Control System is an extremely compact, yet fully
functional control system in the Honeywell TDC3000X family. Figure 1-1 is an
illustration of the basic Enhanced Micro TDC3000 Control System. This control system
communicates to the process via the Honeywell Universal Control Network (UCN). The
process can be monitored and controlled by Program Manager or Advanced Process
Manager.
This manual describes the Enhanced Micro TDC3000 system. The system comes in two
models. The model numbers are:
Model Number
MX-DTAB01
MX-DTAC01
Hardware Components
K2LCN, 1 US, w/APM, 4MW AM, 875 MB HM.
K2LCN, 1 US, w/APM, 8MW AM, 875 MB HM.
The Enhanced Micro TDC 3000 models have the following characteristics and features:
• Only “version A” models (with 1 US node) are offered as the base system. The
old”version B” models (with 2 US nodes) are no longer offered as a base system (the
old”version B” models are equivalent to a “version A” model, plus an optional US
node).
• All nodes are equipped with K2LCN processors.
• The base models will include an Advanced Process Manager (APM) as standard
equipment.
• The minimum AM processor memory is 4 MW (the base system models are offered with
AM nodes in two memory sizes — either 4 MW or 8 MW).
• The US included with the base system has 6 MW processor memory and supports
‘Universal’ personality.
• The US node in the base system is equipped with dual 150 MB Bernoulli cartridge
‘multi-drives’. The new ‘multi-drives’ are compatible with 35 MB
• The HM included in the base system has a 875 MB hard drive and 3 MW processor
memory.
• The NIM included in the base system has 3 MW processor memory.
• The US monitor and printer are not included with the “R500-Ready” Enhanced Micro
TDC 3000 models. These two peripherals have their own model numbers and must be
ordered separately. The operator’s keyboard, however, is included with the base system
model.
• The Enhanced Micro TDC 3000 models will not support UXS or AXM. There are
currently no plans to provide UXS or AXM options with the system.

GENERAL DESCRIPTION
The Enhanced Micro TDC3000 Control System consists of two cabinets (also called
"towers") which together contain the electronics, two cartridge disk drives, and a history
module. The cabinet electronics support up to four color monitors, four keyboards, and
optional touchscreens or trackballs. A printer is also connected to the system.
Two electronics modules, one housed in each tower, provide all of the electronics for the
Enhanced Micro TDC3000 Control System (excluding peripherals). These modules,
called Multinode Modules, are each capable of holding four TDC 3000 Nodes.
Although the Advanced Process Manager (APM) is part of the Enhanced Micro TDC3000
Control System, it is not described in this manual. See subsection 1.5 for a list of
publications that discuss the Advanced Process Manager and the Universal Control
Network (UCN).
Figure 1-2 is a representation of some of the nodes used to construct a sample Enhanced
Micro TDC3000 Control System.

Basic Enhanced Micro TDC3000 Systems
The Enhanced Micro TDC3000 Control System is furnished with one basic version. This
is the single US Micro TDC3000.
The base version consists of two 4-node towers, an operator’s keyboard, an engineer’s
keyboard, a color monitor and printer (ordered seperately), and the Advanced Process
Manager. Four nodes are contained within the two towers:
1. US—UNIVERSAL STATION A window to the process—allows all information
supplied from process-connected devices, instrumentation subsystems, and
computers to be seen and used. The color monitor, two keyboards, an optional
touchscreen or trackball, two cartridge disk drives, and the ASPI-41 printer are
integral parts of the Universal Station.
2. AM—APPLICATION MODULE Performs calculations and control strategies that are
not possible or practical using only process-connected devices. The Application
Module has 4 or 8 megawords of memory.
3. NIM—NETWORK INTERFACE MODULE Connects the Enhanced Micro TDC3000
Control System to a process controller, generally to a Advanced Process Manager.
4. HM—HISTORY MODULE Provides mass storage of software, system data, and