adjuster output only after the pre-position setting has been attained.
RA-70M Theory of Operation
The RA-70M operates in a similar manner to the RA-70A and RA-70P. The basic differences are that the
RA-70M is designed to provide a three-wire potentiometer compatible output and is used in conjunction
with the Basler Manual Voltage Controls to provide an autotracking capability for "bumpless" transfer
between the Auto and Manual operating modes of many exciter systems. A diagram showing the RA-70M
function blocks is shown in Figure 5.
Nulling/Autotracking Input Circuits
This sensing circuit connects to the F+ and F− outputs of the AVR and to the F+ and F− outputs of the
MVC. Both inputs are compared and the difference is sent to the microprocessor for processing and
output as the nulling signal. If Autotracking is enabled, the null output will read zero as long as tracking is
maintained. The field voltage range (32 Vdc, 63 Vdc, or 125 Vdc) is automatically selected. A front panel
LED lights whenever the AVR and MVC are nulled.
Pushbutton/Contact Inputs Circuit
The pushbuttons (front panel switches) provide for front panel control over the Raise, Lower, Pre-position
1. Pre-position 2. Mode Select, and Programming functions. External dry contacts provide the same
functions as the first four pushbuttons on the front panel except for the Programming function, which is
available only by the use of the front panel pushbuttons. The contact inputs allow remote control of the
reference adjuster.