Protective relays are precise measuring devices, the contacts of which
should not be expected to switch large electrical loads.
In some cases, the protective relay can trip a circuit- breaker directly,
or according to coil rating and the number of circuits to be energised.
The MVAJ relay interfaces with the protection to provide: higher contact
additional contacts for tripping multiple circuit-breakers, control functions,
signalling interlocking.
The MVAJ range comprises very reliable hinged armature relays designed
to operate circuit-breaker trip coils. Built to very high specifications, the
MVAJ range a highly flexible and reliable link between the protective relays
and the circuit-breakers.

Models Available
• Trip relays
Trip relays possess a standard hand-reset flag and operate within 10 ms.
Table 1 shows the trip relay versions available
• Control relays
Control relay variants of each trip relay are available. These relays operate within
approximately 15 ms
All relays configured for high burden applications are suitable for DC operation only
Applications
Self-reset relays reset when the initiating signal is removed,
making them suitable for use as trip relays in auto-reclose
schemes and also for general flagging purposes. Hand-reset relays
require manual resetting, making them effective lockout relays
which are commonly used to trip circuit-breakers associated with
transformers. Electrical-reset relays require a voltage to be
applied to the unit to reset the contacts. These relays may be
used in auto-reclose schemes, or where remote resetting of the
relay is required.
Trip Relay
With the exception of the MVAJ 102 time delayed self-reset
relays, all trip relays are suitable for either low burden or high
burden applications.
High Burden Application
These relays, supplied as high burden, are suitable for use in high
security circuit-breaker tripping circuits. The high burden provides
greater immunity to capacitance discharge currents, which can
result at the inception of an earth fault on battery wiring. This
makes the relays particularly suitable for use in distributed
tripping or control relay contact logic schemes, where the
initiating contact may be remote from the relay.
MVAJ 05
When configured for high burden applications, the burden is
either cut off at operation or is economised to a low figure
instantaneously.
MVAJ 10. MVAJ 20
When configured for high burden applications, the burden is
either cut off or is economised to a low figure after a 40-60 ms
time delay. Due to the greater minimum operating current, the
high burden application also permits the use of supervision relays
such as type MVAX 11. where the wiring is at risk. The 40- 60 ms
time delay ensures reliable operation of series elements such as
type MCAA repeat relays.
Type MVAJ 102 relay is specifically designed for applications
requiring a tripping relay which is self-resetting after a nominal
delay of 2.5 seconds. This relay may be used, for example, for
inter-tripping between higher voltage and low voltage circuit
breakers of a large 3-phase power transformer.
This may become necessary when the high voltage circuit
breaker is tripped after a heavy internal fault by protection
which cannot conveniently provide an auxiliary contact with a
dwell time long enough to ensure correct tripping of the low
voltage circuit-breaker.
Typically, the relay is initiated by transformer protection, such as
overall protection, restricted earth fault and Bucholz relays, in
arrangements where both the HV and LV circuit-breakers are to
be tripped simultaneously.
The HV breaker may be expected to trip more quickly than the LV
breaker so the tripping signal is maintained by the delayed reset.
This ensures complete clearance by the LV circuit-breaker, even
though the fault may have been cleared largely by the HV breaker
and the protection has started to reset.
Low Burden Application
These relays are suitable for general applications where the
initiating contact is located close to the relay. When configured
for low burden applications, by removing the external link from
terminals 22 and 24. the burden is either cut off during operation
or is economised to a low figure instantaneously.