Power Engineering 
K-JIANG
NameDescriptionContent
Current Location:

Eaton MTL838B-MBF Analogue Multiplexer Receiver

From:Eaton | author:Mr.Chen | Time :2026-03-30 | 331 view: | 🔊 Click to read aloud ❚❚ | Share:

most appropriate action - either to repeat the original message, to try and diagnose

what has happened to the slave, to set alarms or to take whatever action is most

appropriate.

The data field

The data field transmits a number of hexadecimal values, each in the range 00 to FF.

In ASCII transmission mode this is made up of a pair of characters, in RTU it is a

single character.

A significant aspect of the communication between the master and it's slaves, that is

not defined by Modbus, is the encoding of numerical data. Modbus allows the

manufacturers of devices to determine which data encoding techniques are available

to users of the device. The encoding of data is discussed on page 13.

The data field is used to provide the slave with any additional information needed to

perform the function requested in the query. This would typically be a register address,

a register range or a value. With some functions, the data field is not required and will

not be included in the query.

If no errors occur, the data field of the response is used by the slave to pass data back

to the master.

If an error occurs, the data field is used to pass more information to the master relating

to the nature of the fault detected.

Byte count data

The responses to a number of queries require the slave to inform the master of the

number of data bytes that are being returned in the response, and this requires a

special implementation within the data field.

A typical example of this would be when the master has requested the slave to

communicate the status of a range of registers. The slave responds by repeating the

function code and it's own address, followed by the data field. The first byte of the data

field identifies the number of bytes that are being returned that contain the register

status information.

As was mentioned earlier, ASCII mode requires two 8-bit bytes to communicate a

single register content, compared to RTU which only requires a single 8-bit byte. This

difference is ignored when the byte count field is calculated, and the number of bytes

indicated is identical to the number of bytes communicated in RTU mode, but is half

the actual number of bytes communicated in ASCII mode.

The error check field

The error checking technique employed on the Modbus network depends on the

transmission mode selected. With ASCII the technique used is based on an LRC

(Longitudinal Redundancy Check) and with RTU a CRC (Cyclical Redundancy Check).

In both cases, the characters transmitted in the error check field are calculated by the

transmitting device and included in the resulting transmission. The receiving device

calculates what the error check field should contain, on receipt of the message, and

compares it with the error check field in the received message. If these two values do

not match exactly, then the receiving device knows that it has not received the

message correctly, and disregards it.

In both modes, parity checking can be optionally selected.

A fuller explanation of the error checking techniques used by Modbus is given in

Appendix A.

Data Encoding and Scaling

As has been mentioned earlier, an important area of the communication along the

network, that is not defined by the Modbus protocol, is the encoding of numerical data.

A related problem is the adoption of a scaling system for the data once it has been

encoded. (Note: this is an area which requires careful consideration by users of the

MTL838B-MBF.)

There is no problem here for manufacturers who are supplying complete systems,

based on the Modbus network, as they can select a data encoding and scaling system

appropriate to their needs. However, for manufacturers who are supplying products for

general use, there is no possibility that they will be able to determine which data

encoding system will be used by their customers, and they must allow the data

encoding technique to be user selectable.

Three data encoding techniques are the most popular - IEEE, 16-bit unsigned and 16

bit offset.

A further area of difficulty associated with the encoding of data is the way in which the

data is scaled - to provide a resolution of the measured value appropriate to the

  • Basler Electric BE1-67 / BE167 DIRECTIONAL OVERCURRENT RELAY
  • Basler Electric BE1-25/79TR Reclosing Relay BE1 25 79TR
  • Basler Electric Contact Expansion Module CEM-2020
  • Basler Electric MVC-300 MANUAL VOLTAGE CONTROL UNIT 9121000106
  • Basler Electric KR2FF Voltage Regulator 9 1163 00 109
  • Basler Electric BE1-81O/UT3EE1YA9S0F / BE181OUT3EE1YA9S0F
  • Basler Electric BE1-87G-G1E-A1K-A0N0F / BE187GG1EA1KA0N0F
  • Basler Electric BE1-47NE3EA1PA0N2F / BE147NE3EA1PA0N2F
  • Basler Electric BE1-81-T1E-E1C-B0N1F / BE181T1EE1CB0N1F
  • Basler Electric BE1-25 SYNC-CHECK RELAY M1E A7P A5N3F
  • Basler Electric BE1-40Q Solid State Protective Relay/ Loss Of Excitation Relay
  • Basler Electric OVERCURRENT RELAY, BE1-50/51M-104
  • Basler Electric MVC 232 MANUAL VOLTAGE CONTROL 9037000103
  • Basler Electric SSE-N 250-9 KW Shunt Static Exciter-Regulator
  • Basler Electric, Solid State Protective Relay, BE1-60
  • Basler Electric SR4A-2B15B3A Static Voltage Regulator 120vac Includes U6250MKG1L
  • Basler Electric BE1-50BF Breaker Failure Relay
  • Basler Electric BE1A1HF1JD1S2F / BE1A1HF1JD1S2F
  • Basler Electric BE1-81O/UT3EE1JA7N2F / BE181OUT3EE1JA7N2F
  • Basler Electric EXCITER DIODE MONITOR EDM-200
  • Basler Electric DECS125-15-B2C5 DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric OVER CURRENT RELAY 9252000107
  • Eaton Sag Ride-Through power conditioner
  • Eaton Sag Ride-Through power conditioner
  • Eaton Power-Sure 800
  • Eaton Power-Sure 700
  • Eaton Power-Suppress 600
  • Eaton T100H-2500-5HC PWR SUPPRESS T100 HW 2.5KVA, 50 HZ, 55DEG C MAX
  • Eaton T100H-1800 PWR SUPPRESS T100 HW 1.8KVA
  • Eaton 9468-ET IS Ethernet Isolator
  • Eaton 9466-ETA IS Ethernet Managed Switch
  • Eaton 9466-ET IS Ethernet Managed Switch
  • Eaton 9465-ETA-S-SC IS Media Converter Single-mode
  • Eaton 9465-ET-M-ST IS Media Converter Multimode
  • Eaton 9465-ET-S-SC IS Media Converter Single-mode
  • Eaton 9465-ET-M-SC IS Media Converter Multimode
  • Eaton 9461-ET IS Serial to Ethernet Gateway
  • Beckwith Electric M-0067E Tapchanger Control
  • Beckwith Electric M-2001D Digital Tapchanger Control
  • Beckwith Electric M-2001C Digital Tapchanger Control
  • Beckwith Electric B-1500 Battery Backup Power
  • Beckwith Electric B-2083 SmartBank Three Phase Junction Box
  • Beckwith Electric M-2017 Capacitor Bank Discharge Tool
  • Beckwith Electric M-2980A Weatherproof Capacitor Control Cabinet
  • Beckwith Electric M-6283A Three Phase Digital Capacitor Bank Control
  • Beckwith Electric M-6280A Digital Capacitor Bank Control
  • Beckwith Electric M-4272 Digital Motor Bus Transfer System
  • Beckwith Electric M-3420 Generator Protection Relay
  • Beckwith Electric M‑0193B Syncrocloser® Unit
  • Beckwith Electric M-3520 Intertie Protection Relay
  • Basler Electric BE1-25 Sync-check Protective Relay
  • Basler Electric RDP-110 REMOTE DISPLAY PANEL
  • Basler Electric SSR 125-12 VOLTAGE REGULATOR 9185900102 WITH MODULE 9261500101
  • Basler Electric BE1-851 OVERCURRENT PROTECTION RELAY MECHANISM G3A1S1N
  • Basler Electric 149D930G02 / 149D930G02
  • Basler Electric BE1-81O/UT3EE1LB7S1F / BE181OUT3EE1LB7S1F Digital Frequency Relay
  • Basler Electric BE1-51/27CA1EZ10A0N0F / BE15127CA1EZ10A0N0F Time Overcurrent Relay
  • Basler Electric 149D956G02 / 149D956G02
  • Basler Electric BE1-51A / BE151A Overcurrent Relay
  • Basler Electric BE1-40Q-F3E-E10-A0N0F / BE140QF3EE10A0N0F
  • Basler Electric RDP-110-S1 Generator Annuciator
  • Basler Electric DECS-300 DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric - DECS-200-1C - Digital Excitation Control System
  • Basler Electric DECS125-15 Digital Excitation Control System with Power Module
  • Basler Electric BE1-87G Variable Percentage Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric / Kohler BE1-11g Generator Protection Relay G5A3M2J2N0E000
  • Basler Electric BE1-81O/UT3ED1JA7N2F / BE181OUT3ED1JA7N2F
  • Basler Electric BE1-81O/UT3EE1YB7N1F / BE181OUT3EE1YB7N1F
  • Basler Electric DECS-200 -1L DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric DECS 125-15-B2C1 V.2.0.9 DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric 9507900205 SSR Retrofit Static Voltage Regulator
  • Basler Electric BE2000E Digital Volatge Regulator
  • BASLER DECS-250-CN1CN1N DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric DGC-2020 Digital Genset Generator Controller Panel Enclosure
  • Basler Electric BE1-81O/UT3ED1LA7N0F / BE181OUT3ED1LA7N0F
  • Basler Electric BE1-81O/UT3EE1YA9S0F / BE181OUT3EE1YA9S0F
  • Basler Electric BE1-81O/UT3EE1YA6N1F / BE181OUT3EE1YA6N1F
  • Basler Electric DECS125-15 DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric BE1-951 OverCurrent Protect System
  • Basler Electric BE1-700V Digital Protective Relay N3N2X1N
  • APR63-5 Basler Electric Automatic Voltage Regulator
  • Basler BE1-851 overcurrent relay
  • Basler Electric BE1-87T Transformer Differential Relay Module
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler Electric 9310300100 DECS-300 Digital Excitation Control System
  • Basler Electric SSE-N 125-4.5KW SHUNT EXCITER REGULATOR
  • Basler Electric DGC-2020HD-5NS1DNSBA Digital Genset Controller
  • Basler Electric BE1-81-O/UT3EE1JB7N1F / BE181OUT3EE1JB7N1F
  • Basler Electric BE1-81T1EE1WA0N1F / BE181T1EE1WA0N1F
  • Basler Electric BE1-25M1EA6PN5R1F / BE125M1EA6PN5R1F
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-250-LN1SN1N DIGITAL EXCITATION CONTROL SYSTEM
  • Basler Electric DECS-250 - CN2CN 1N Digital Excitation Control System Unit
  • Basler Electric Relay BE1-50/51B-207 Overcurrent Relay
  • Basler Electric DECS-300-C0N0 DIGITAL EXCITATION CONTROL SYSTEM
  • DECS-200-1C Digital Excitation Control System
  • Basler Electric DECS-200N-C1 Negative Forcing Digital Excitation Control System
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS-250 DIGITAL EXCITATION CONTROL SYSTEM DECS-250-LN1CN1N
  • Basler Electric DECS-250 LN2SA1D Digital Excitation Control System Unit
  • Basler Electric BE1-87T-A1E-A1J-D0S1F / BE187TA1EA1JD0S1F
  • Basler Electric BE1-11-G6D1M0J2P0E000 / BE111G6D1M0J2P0E000
  • Basler Electric BE1-GPS100-E4N1H1N / BE1GPS100E4N1H1N
  • Eaton Omnex T300-000272 T300 Series Remote Controller
  • EATON ELPRO 450U-E Wireless Ethernet Modem Model: 450U-E-L-440-W
  • Eaton JD3225 Series C complete molded case circuit breaker
  • Eaton HMP-HM64 Crouse-Hinds series MTL HART backplane
  • EATON VICKERS EEA-PAM-523-A-32 02-326001 POWER AMPLIFIER
  • Eaton HTP-SC16M / MTL Hart Multiplexor Connection Unit
  • Eaton XV-152-D6-10TVR-10 150609 Touch Panel
  • Eaton S801+ soft starter S801+N66N3S-MA
  • Eaton Series C complete molded case circuit breaker EHD3015L
  • Eaton V200M4CJC NEMA starter, Space SVG reversing starter
  • EATON CORPORATION CAN-16DI/P / CAN16DIP
  • Eaton Soft Starter S801+N66N3S
  • Eaton Soft Starter S801+N66N3S
  • Eaton XV-303-70-B00-A00-1B Base HMI XV300 Single Ethernet
  • EATON XV-303-70-B00-A00S07 / XV-303-70-B00-A00S07
  • EATON CUTLER-HAMMER MP-3010 SAFETY RELAY 66D2205G01 MP-3000
  • EATON CUTLER HAMMER 92-02123-00 7600C OPERATOR INTERFACE PANELMATE BLIND NODE EP
  • EATON CORPORATION HMCP150T4CBP10 CIRCUIT BREAKER
  • Eaton 142531 XV-102-D6-57TVR-10 Touch Panel
  • EATON ELECTRIC CAN-16DO/0.5A-PK 140254 CanOpen digital output 0.5A
  • EATON XV-102-B5-35TQR-10-PLC 140021 XV102B535TQR10PLC
  • EATON MP-3000 66D2032GX1 NSNP
  • Eaton HFD3150 3P 150A 600VAC Circuit Breaker
  • Eaton Cutler-Hammer HFD3030 6639C86G87 3 Pole 30A 600V Circuit Breaker