Mp-3000 motor protection
Applications
• Protection for three-phase AC motors
• Medium and large motors
• Motors with high inertia loads
• Motors with reduced voltage starting
Protection functions
• I2t overload protection (49/51)
• Locked rotor (49S/51)
• Ultimate trip current (51)
• Negative sequence phase unbalance (46)
• Instantaneous overcurrent (50)
• Ground fault protection (50G)
• RTD trip and alarm with URTD module (49/38)
• Underload trip (37)
• Starts per time (66)
• Jam or stall (51R)
• Auto or manual reset (86)
• Failsafe or non-failsafe trip modes
• Alarming
• Control
• History
Monitored values
• Motor currents
• RTD temperatures
• Motor conditions
Communications
• Optional interface capability to computer network for data
collection, storage and/or printout via the Cutler-HammerT
PowerNetE system
Physical characteristics
• User-friendly interface
• Large LED display
• Optional quick-release drawout case
• Height: 10 .25 inches (260 .4 mm)
• Width: 6 .72 inches (170 .7 mm)
• Depth: 2 .54 inches (64 .5 mm) without PONI, 4 .39 inches
(111 .5 mm) with PONI
Standards and certifications
• ULT recognized (file number E154862)
• UL 1053 recognized
• UL 508 recognized
• ANSI C37 .90. C37 .90 .1. C37 .90 .2
• CSAT
General description
Eaton’s Cutler-Hammer MP-3000 motor protection relay is a multi
functional microprocessor-based protective relay for the protection
of any size motor at all voltage levels . It is most commonly applied
on medium voltage or larger motors . The MP-3000 relay is a current-
only device that provides complete and reliable motor protection,
monitoring, and starting control functions .
The MP-3000 motor protection relay is available in either a fixed
mount, semi-flush case or in a semi-flush quick release drawout
case . Both housings are compact and fit a standard IQ cutout .
The optional quick release drawout case features two-stage contact
disconnects and self-shorting CT circuit terminal blocks . A spare self
shorting terminal pair is available for use as a relay removal alarm or
for continuous motor operation (non-failsafe mode) on relay removal .
The optional communication module is externally mounted on the
fixed mount case and internally mounted in the drawout case .
The MP-3000 motor protection relay has three-phase and one
ground current inputs . Both a 5A and 1A version are available . The
ground protection and metering functions can be used with either
a zero sequence ground CT or from the residual connection of the
phase CTs . The zero sequence ground CT provides greater ground
fault sensitivity than the residual connection . The unit is user-
programmable for 60 Hz or 50 Hz operation .
The MP-3000 motor protection relay has two discrete inputs, four
Form C (1 NO and 1 NC) contacts and one 4 to 20 mA analog
output . A fused source is available for the discrete inputs on the
MP-3000 . This eliminates additional control circuit wiring . The relay
provides maximum user flexibility to configure the I/O . All inputs
and outputs (except for the trip output) are user-programmable . In
addition, the relay has 10 LEDs for the indication of protection on,
program mode, monitor mode, view setting mode, history mode, log
mode, trip, alarm, auxiliary 1 and auxiliary 2 operation . Monitor mode
provides display indication of the discrete input states . The program
mode provides testing of the output relays, target LEDs, and
analog circuit .
A user-friendly operator interface and display provides quick access
to the settings, monitored values, motor history, and operational
logs . The large LED alphanumeric character display provides easy
viewing from any angle in any light . Simple keypad operation pro
vides quick and easy navigation through all settings and stored data .
The program mode and emergency override buttons are access
restricted via a seal and latched cover . An integrated help function
provides an online description display of functions, abbreviations,
and operations .
optimum motor protection
The MP-3000 motor protection relay has been designed for maxi
mum motor operation and protection . It permits running the motor
close to its design limits while protecting it against excessive
heating and damaging overload conditions . The MP-3000 field-
proven protection algorithms were developed based on motor
designs and operating parameters for optimum operation and
protection while minimizing nuisance tripping .
The MP-3000 motor protection relay utilizes a patented protection
algorithm and measurement technique based on proven positive
and negative (unbalance) sequence current sampling and true Rms
calculations .
Features
• Built-in help program
• Built-in test mode
• LED indication
• Microprocessor-based
• Self diagnostics
• Programmable binary inputs
• Programmable outputs
• Real-time clock