condition.
• Refer to the paralleling diagrams in the LTC Comprehensive System Manual for the
following conditions:– If circuit breakers such as the "52 Line Breaker(s)" and the "24
Tie Breaker(s)" as shown in the paralleling diagrams are present, then their auxiliary
contact connections should be included as shown to ensure proper automatic transfer
from parallel to independent operations. Please note that auxiliary breaker contacts
are shown in the parallel mode with all breakers closed.
– If these breakers do not exist, and for example, only one common load breaker is
used, the circuit should be wired to make a circuit where the normally closed contacts
are shown. No circuit should be made where the normally open contacts are shown.
• If paralleling and hand‑operated load switches are used:
a. AUTO/MANUAL switches on the M‑2270. M‑2278. M‑2280. and other Beckwith
Electric adapter panels should be placed in the MANUAL position.
b. Other controls should be placed in the MANUAL position.
c. The M‑0115A PARALLEL/ INDEPENDENT switch should be placed in the
INDEPENDENT position before the load switches are operated (see CAUTION).