GENERAL
This document describes the system configurations,
development/maintenance, software configurations,
and network specifications for the FCN autonomous
controllers with NFCP501/NFCP502 CPU module in
the STARDOM. (FCN is an acronym for field control
node.)
Notation in this document:
• The term “FCN” refers to the module consisting type
autonomous controllers.
• The term “FCN-500” refers to the autonomous
controllers with NFCP501/NFCP502 CPU module.
• The term “FCN-100” refers to the autonomous
controllers with NFCP100 CPU module.
• The term “FCN-RTU” refers to the low power
autonomous controllers with NFCP050 CPU module.
• The term “FCJ” refers to the all-in-one type
autonomous controllers.

FCN-500 is a controller consisting of CPU, I/O, and
other modules as necessary. It supports a variety of I/O
modules with excellent scalability. And, highly reliable
system can be configured with duplex power supply
modules, CPUs, control network system.
For hardware details, refer to FCN Autonomous
Controller Hardware (FCN-500), GS 34P02Q14-01E.
FEATURES
l High Performance
• Applicable to a variety of processes, from sequence
control processes to analog control processes.
• Intercommunication with other autonomous
controllers or other equipment for inter-linked control
actions, in addition to stand-alone operation.
• Using Versatile Data Server Software (VDS) or
SCADA Software (FAST/TOOLS) together allows
a system with enriched operation and monitoring
functions to be built up.
• An FCN/FCJ OPC server for Windows can be used
for accessing the data of an FCN/FCJ from an OPC
(OLE for Process Control) client on a PC.
• Duolet application is Java language application and
enables users to implement the following functions
on FCN-500; displaying images on a Web browser,
saving data files, transferring files using the FTP
protocol, sending/receiving e-mails and public
network connection using the PPP protocol.
l High Reliability
• RAS features (CPU self-diagnostics, temperature
monitoring, I/O diagnostics, and more)
• Memory with error-correcting code (ECC)
• Low heat dissipation, eliminating the need for a
cooling fan
• The Ethernet control network, CPU, power supply
module, and E2 bus/SB bus (FCN local bus) can all
be duplexed for an FCN-500.
l Engineering Efficiency
• Five IEC 61131-3 compliant programming languages
are supported, enabling the user to selectively use
these languages according to their purposes of use
and applications.
• Control logic can be encapsulated into software
parts for reuse, allowing efficient and quality system
configuration.
• Application Portfolios packed with Yokogawa’s
application expertise, enable easy implementation of
advanced functions, including control-loop instrument
blocks and communication with PLCs.
l Easy Maintenance
• Online download function allows a control application
to be modified during system operation
• All modules are hot-swappable with an FCN-500.
CONFIGURATIONS
l System Configurations
FCN-500 is locally mounted controllers to allow diverse
systems to be configured according to the individual
users’ work sites; however, the possible system
configurations can be broadly divided into three types:
• A system consisting of a standalone FCN-500
• A system in which FCN-500s are connected to
each other through the control network and perform
interlinked actions (up to a total of 15 FCNs and FCJs
can intercommunicate with one FCN/FCJ).
• A system in which one or more FCN-500s are
interlinked with VDS, FCN/FCJ OPC Server or FAST/
TOOLS.
VDS and FCN/FCJ OPC server, FAST/TOOLS can
be connected up to 8 units in total. The FCN/FCJ
OPC server counts as 2 units because the DA server
and AE server operate. The FAST/TOOLS with
duplexed network counts as 2 units.
Development and Maintenance of FCN-500
A PC/AT-compatible computer is used for development
and maintenance of applications for an FCN-500.
Resource Configurator is a tool program to be installed
in the computer used for maintenance, and is used to
make the FCN-500 hardware settings.
The user can access FCN-500s via a Web browser
from a PC to make detailed settings for the network
and so on, and to perform maintenance operations
such as database backup and restoration.
Logic Designer is a tool program for the development
of control applications (IEC 61131-3) for an FCN-500.
Logic Designer requires a license to run.
wechat/whatsapp:
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved