Introduction
Read these instructions carefully and inspect the equipment to
become familiar with it before trying to install, operate, service, or
maintain it .
Electrical equipment should be installed, operated, serviced, and
maintained only by qualified personnel . Local safety regulations
should be followed . No responsibility is assumed by Eaton for any
consequences arising out of the use of this material .
Eaton reserves right to changes without further notice .

Abbreviations
CB – Circuit breaker
CBFP – Circuit breaker failure protection
EMC – Electromagnetic compatibility
EPROM – Erasable programmable read only memory
HW – Hardware
LED – Light emitting diode
LV – Low voltage
ms – Millisecond
MV – Medium voltage
NC – Normally closed
NO – Normally open
PMSG – Permanent magnet synchronous generator
Rx – Receiver
SF – System failure
SW – Software
Tx – Transceiver
uP2– Microprocessor
General
The Eaton arc flash relay 101C (EAFR-101C) is a sophisticated
micro-processor based arc flash protection relay including complete
self-supervision functionality . It is designed to minimize the damage
caused by an arcing fault (arc flash) by sensing light from the point
sensor and acting to trip the circuit breaker sourcing the fault
current . The EAFR-101C complete system self-supervision function
provides the highest level of dependability by continuously monitor
ing all internal system functions along with external connections .
The EAFR-101C is designed according to the latest protection relay
standards and is therefore suitable for installations in rough environ
ments, such as utility, traditional or renewable power plants, off
shore, marine, oil and gas, mining, steel, or any other heavy industry
applications . It is also well suited for commercial and institutional
electrical systems . The EAFR-101C is suitable for either medium
voltage or low voltage switchgear and motor control center applica
tions in both new and retrofit installations .
EAFR-101C features
The EAFR-101C is a multipurpose arc flash protection relay that can
receive light from four different channels of light point sensors and
can be applied for variety of applications . The EAFR-101C can be
used as a stand-alone relay or as part of a more complex arc protec
tion system through the binary bus .
Main features of EAFR-101C:
• (110-220) Vac / (125-250) Vdc auxiliary power supply;
• (18-72) Vdc optional power supply;
• Four arc point sensor channels (S1. S2. S3. and S4);
• Six binary inputs (BI1. BI2. BI3. BI4. BI5. and BI6) nominal voltage
of 24 Vdc;
• Three normally open trip relay outputs with direct trip circuit rated
contacts (T1. T2. and T3);
• One normally open electronic lock-out trip relay with direct trip
circuit rated contacts (T2);
• Two 24 Vdc binary outputs (BO1 and BO2);
• One system failure relay, form C output (SF);
• 16 indication LEDs; and
• One push-button (SET)
Operation and configuration
LED indicator functions
The EAFR-101C contains 16 indication LEDs . A user definable text
pocket can be slid in under the label for identifying each LED func
tion (except POWER and ERROR LEDs) . LEDs are located at the
front plate of the relay for clear viewing without a need for opening
doors .
During power up, the relay performs an LED test . All LEDs are
turned on for two seconds and then off . Only the blue POWER LED
will remain on . After powered up, the relay goes into protection
mode in 50 ms even while the LED test is being performed .
During normal operation, the blue power LED is ON, as are any CB
open/close status LED’s for connected CB’s .
The sensor LEDs are off during the inactive condition . If a point arc
sensor is activated, the corresponding sensor channel LED will turn
on if the activation is longer than 1 .5 ms . The sensor LED activation
function is latched (steady light) . To clear the LED, the “SET” button
should be pressed .
In case of a loose sensor wire and binary input wires or configura
tion mismatch (new sensor attached without running auto-configu
ration system setup (see Section 3 .3 .1) situation, the corresponding
LED for that sensor will start flashing and the ERROR LED will
activate .
The Binary I/O LEDs indicate the I/O-line status . If any of the lines
become active for more than 1 .5 ms, the corresponding LED will
turn on (latch) .
In a trip situation, the corresponding trip LED will turn on . Trip
outputs are controlled by the dipswitch settings (see Section 3 .5) .
All activation and trip indication LEDs are latched, even if the
dipswitch setting is in the non-latched mode . They have to be
cleared by pushing the “SET” button .
LED indications are stored in non-volatile EPROM memory for iden
tifying the trip information in case the auxiliary power is lost . When
re-powering the relay after power supply loss, the actual LED status
can be visualized from the front of the relay
wechat/whatsapp:
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved