APACS+ Subsystems
An FCP280. FCP270 or FCM100Et/FCM100E
baseplate is installed in the MODULPAC enclosure
with single or redundant modules. The baseplate has
a built-in Fieldbus termination assembly. The
I/O module power supplies and MODULRACs are
retained in the cabinet.
The MODULRACS, used to house I/O modules, are
reused to house the DCS FBMs. All termination
assemblies in the local, adjacent, and remotely
marshalled MODULPACs remain intact with their
termination cables and field wiring.

APACS+ I/O modules are removed from the
MODULRAC and replaced by a corresponding DCS
FBM that mates to the original power/signal
connector and termination cable connector on the
back of the MODULRAC. This DCS FBM provides
original I/O functionality of the process inputs and
outputs.
Ladder Logic Implementation
Ladder logic for an APACS+ system is implemented
in the ACM controllers, not in the I/O modules. Thus,
any digital I/O point in the system can be used as an
input or output to the ladder logic running in the
ACM. A similar capability exists with the migrated
APACS+ system through the use of sequence control
logic in the FCP280. FCP270 or ZCP270 Control
Processor.
Foxboro control block ladder logic is implemented by
using a combination of logic which executes directly
in the digital I/O modules and sequence control logic
in the Control Processor. This same capability exists
in the AID115. AID230. AOD115. and ADO125
APACS+ migration modules. The channel
configurable ASAM01. AEAM01. ASDM24 and
ASDM48 I/O modules implement ladder logic only by
using sequence control logic in the Control Processor
similar to the original APACS+ system.
Migration with FCP280 and DCS FBMs
The Field Control Processor 280 (FCP280) is a
distributed, field-mounted controller module that
supports up to 128 DCS FBMs - 32 per HDLC
fieldbus. The FCP280 connects to the control
network via optionally redundant 100 Mbps Ethernet
fiber optic cables and Ethernet fiber switches. The
FCP280 is an optionally fault-tolerant controller that
communicates with connected DCS FBMs to
perform data acquisition and control using Foxboro
Evo control algorithms.
The FCP280 mounts in a 2-position baseplate that
supports a single module or a fault-tolerant module
pair. The baseplate accepts only FCP280 modules.
The FCP280 connects to an optionally redundant
2 Mbps HDLC I/O Fieldbus for communications to
the DCS FBMs and provides galvanic isolation
between the 100 Mbps Ethernet Fieldbus and the
2 Mbps local Fieldbus.
FCP280 modules connect to a pair of copper or fiber
optic network adapters that connect to Ethernet
switches in a redundant control network. The
network adapter pair mounts to the FCP280
baseplate.
To support redundancy, a pair of FCP280s must be
used for each DCS FBM grouping. In non-redundant
configurations, only a single FCP280 is required for
each grouping.
The maximum total cable length for the 2 Mbps
Fieldbus is 60 m (198 ft) within a grouping.
I/O Modules
The DCS FBMs provide advanced 200 Series FBM
technology on an APACS+ module form factor. Each
DCS FBM plugs into the slot used by the replaced
APACS+ module and provides two rear connectors,
one of which mates to a connector on a local field
termination strip on the backplane of the
MODULRAC.
For marshalled termination assembly located in an
adjacent MODULPAC enclosure, the DCS Fieldbus
Module I/O connector mates to a field termination
cable connector mounted on the back of the
MODULRAC.
The following I/O module types are used in the
APACS+ system:
Analog input module
Analog multi-range input module
Analog RTD input module
Digital input module
Digital output module
HART® input module
HART redundant input module
Analog/digital/pulse input and analog/digital
output module, configurable point-by-point
Analog/digital input and analog/digital output
module, configurable point-by-point
Digital input/output, configurable point-by-point.
Each module type is replaced with an equivalent
Foxboro Evo DCS FBM module. All I/O wiring
connected to the I/O module termination strips
remain in place. Power is derived from the original
rack power supply. Table 1 lists the available DCS
Fieldbus Modules and the APACS+ modules they
wechat/whatsapp:
Email: kongjiangauto@163.com