the relay. Control power must be applied for this function to operate. The pushbuttons are recessed
behind the relay front panel and are not accessible with the cover installed.
TARGETS
One target is included for each tripping function as specified by style number. Targets are operated either
by the internal signal initiating tripping (internally operated) or by a minimum of 200 mAdc flowing through
the series circuit consisting of the target coil and output relay contacts (current operated). Within a
specific relay, all targets must be operated in the same way.
POWER SUPPLY OPTIONS
Various power supply options are available to allow the BE1-67N relay to be used with standard supply
voltages. See the style chart for details.
POWER-UP DELAY
A power-up delay timer is initiated upon application of control power to the relay to prevent undesired
contact transitions when sensing signals are present. Operation of measuring circuits and output circuits
are inhibited (less than 0.5 seconds) until the power-up delay period has expired.