Overview
The BE1-59NC relay provides sensitive protection for capacitor banks.
Features
• Sensing circuit rejects harmonics and noise to achieve higher
sensitivity to 50/60 Hz neutral voltage.
• Includes an early warning alarm output on minor unbalances such as a
blown fuse.
• Can be set to trip when voltage across any capacitor exceeds 110% of
nominal.

Benefits
• Helps avoid cascading capacitor failures.
• Minimized PT costs as a result of low sensing burden.
• Reduced battery load with low burden power supply.
• Accurate, repeatable, and reliable operation.
• Simple HMI provides clear and intuitive settings for easy
configuration.
• LED targets provide clear annunciation of status.
• Easily perform in-case system and device tests using test plugs.
BE1-59NC Neutral Overvoltage Relays provide sensitive protection for
capacitor banks. There are three common types of capacitor bank failures
that BE1-59NC relays recognize. They are:
• Unit dielectric failure
• Capacitor bank insulator failure
• Blown fuses
BE1-59NC relays protect for overvoltage due to internal voltage shifts
that occur as a result of these types of failures.
Application
Capacitor banks are widely used by utilities to maintain specified system voltage.
Addition of capacitive loads at appropriate points on the system compensate for
heavy inductive loading that normally tends to reduce voltage.
This adding of leading megavars to compensate for the lagging megavar
component of electric loads is frequently referred to as power factor correction.
Capacitor banks must be switched in response to actual load conditions in order
to obtain maximum power factor correction benefits.
Capacitor Bank Switching
One of the common methods of maximizing capacitor bank benefits is by evaluating
the bus voltage. A bandwidth surrounding the desired bus voltage level is
established. When the bus voltage falls below the bandwidth level, the capacitor
bank is switched into the circuit. When the bus voltage rises above the bandwidth
level, the capacitor bank is switched out.
Protection
Protection of capacitor banks has always been difficult. It is especially difficult to
sense failures inside the capacitor banks because of the configuration.
Experience indicates that most capacitor bank faults involve one or more insulator
failures with arcing across groups and/or phase-to-phase inside the bank. In most
cases, these types of faults are not seen by the bus differential or other protection
unless the arcing spills over to the area between the fuses and the circuit switcher.
A fault across an insulator usually means that one or more groups of parallel units
are shorted. This will cause a neutral shift and unbalanced phase currents.
Unbalanced phase current magnitudes are determined by the number of series
connected groups. For full phase-to-neutral flashover, the maximum phase current
is three times normal capacitor bank load in the faulted phase.
One main protection concern is overvoltage cascading. A capacitor bank is unique
in that cascading of units may take place after a predetermined number of unit
fuses have operated. Normally after a fuse has blown in any other type of equipment,
the faulted apparatus is disconnected and usually does not affect any remaining
equipment that is in service. That is not so with a capacitor bank. Each fuse that
blows to isolate the faulted unit sets up an increased voltage stress on the remaining
units (Figure 1-1). Sometime later, the next weakest unit in that group fails.
As each successive fuse blows, the voltage increases another step and rapidly causes
the next unit to fail. Cascading takes place and results in serious damage to the
capacitor bank and possible hazards to personnel. While the capacitor bank is failing,
the station in minimally affected. The voltage is nearly normal, the current flow is almost
unaffected, and station relay protection is not taking any action until the failure has
developed into a phase-to-phase or phase-to-ground fault.
A solution was to develop a protective scheme for the capacitor bank with the main
emphasis on preventing overvoltage cascading. To do this, a ground fault relay or neutral
shift device had to be developed that was sensitive enough to detect blown fuses for both
alarming and tripping purposes. The best place to obtain the sensing information is
between the neutral of the capacitor bank and ground.
Voltage differentials between the normal capacitor bank status and that of one blown
fuse are very small.
However, BE1-59NC relays are sensitive enough to differentiate between these conditions
and act decisively.