emphasis on preventing overvoltage cascading. To do this, a ground fault relay or neutral
shift device had to be developed that was sensitive enough to detect blown fuses for both
alarming and tripping purposes. The best place to obtain the sensing information is
between the neutral of the capacitor bank and ground.
Voltage differentials between the normal capacitor bank status and that of one blown
fuse are very small.
However, BE1-59NC relays are sensitive enough to differentiate between these conditions
and act decisively.